(A) Application parameters
Parameters
5 - 370
●
Calibrating set point input
Apply the input (for example, 0 V) of set point setting 0% across terminals 2 and 5.
Using C2 (Pr. 902), enter the frequency (for example, 0 Hz) to be output by the inverter when the
deviation is 0%.
Using C3 (Pr. 902), set the voltage value at 0%.
Apply the input (for example, 5 V) of set point setting 100% across terminals 2 and 5.
!
Using Pr. 125, enter the frequency (for example, 60 Hz) to be output by the inverter when the
deviation is 100%.
Using C4 (Pr. 903), set the voltage value at 100%.
●
Calibrating measured value input
Apply the input (for example, 4 mA) of measured value 0% across terminals 4 and 5.
Perform calibration by C6 (Pr. 904).
Apply the input (for example, 20 mA) of measured value 100% across terminals 4 and 5.
Perform calibration by C7 (Pr. 905).
●
The figure below shows the results of having performed the calibration above.
Example
To enter the set point on terminal 2
NOTE
When the set point is set at Pr. 133, the setting frequency of C2 (Pr. 902) is equivalent to 0% and
the setting frequency of Pr. 125 (Pr. 903) is equivalent to 100%.
NOTES
Set the frequencies set at C5 (Pr. 904) and Pr. 126 to each of the same values set at C2 (Pr. 902) and
Pr. 125.
The display unit for analog input can be changed from "%" to "V" or "mA". (Refer to page 5-269.)
I002695E, I002696E, I002697E
Fig. 5-174:
Input calibration
100
0
0
5
(%)
100
0
0
20
(%)
4
60
0
0
100
[Set point setting]
[Measured value]
[Manipulated variable]
Manipulated variable (Hz)
Deviation (%)
(mA)
(V)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......