Parameters
(A) Application parameters
FR-F800
5 - 349
●
When the number of times of cleaning operation is an odd number, the operation in the opposite
direction to the start command is performed. When the number of cleaning times is an even
number, the operation in the start command direction is performed.
●
When the motor rotation direction is restricted in Pr. 78 "Reverse rotation prevention selection",
rotation is performed not in the prohibited direction but in the permitted direction.
●
Use Pr. 1472 "Cleaning reverse rotation frequency "and Pr. 1474 "Cleaning forward rotation
frequency" to set the running frequency for cleaning operation, and use Pr. 1473 "Cleaning reverse
rotation operation time" and Pr. 1475 "Cleaning forward rotation operation time" to set the
operating time after the cleaning running frequency is reached.
●
Use Pr. 1477 "Cleaning acceleration time" and Pr. 1478 "Cleaning deceleration time" to set the
acceleration/deceleration time during cleaning operation.
●
Y215 signal turns ON during cleaning operation. For the Y215 signal, assign the function by setting
"215 (positive logic)" or "315 (negative logic)" in any of Pr. 190 to Pr. 196 (output terminal function
selection).
Cleaning trigger selection (Pr. 1471, Pr. 1479, X98 signal)
●
Use Pr. 1471 "Cleaning trigger selection" the trigger to start cleaning operation. As set in Pr. 1471,
cleaning operation is started when any of the applicable trigger conditions is satisfied.
The ON state at power-ON or inverter reset is not regarded as a trigger.
Use Pr. 150 and Pr. 151 to set the detection level. (Refer to page 5-244.)
Use Pr. 131, Pr. 132, Pr. 1143, and Pr. 1144 to set the detection level. When the frequency reflection
is not provided for the PID setting, or when the function is disabled, a trigger does not occur. (Refer
to page 5-353.)
I003037E
Fig. 5-156:
Output frequency with reverse rotation prevention
Pr. 1471 setting
Trigger factor
Value in each bit
Remarks
0
1
Bit 0
Start trigger
Trigger disabled
Trigger enabled
Turning ON of the start command is defined
as a trigger.
$
Bit 1
Output current
Trigger disabled
Trigger enabled
Turning ON of Y12 signal is defined as a
trigger.
!
Bit 2
PID upper/lower
limit
Trigger disabled
Trigger enabled
Turning ON of FUP, FDN, FUP2, or FDN2 signal
is defined as a trigger.
!
Bit 3
Load warning
Trigger disabled
Trigger enabled
Turning ON of LUP or LDN signal is defined as
a trigger.
!
—
X98 signal input
—
Turning ON of X98 signal is defined as a
trigger. (This trigger is always enabled by
assigning X98 signal to an input terminal.)
—
Time trigger
—
When Pr. 1479
≠
"0", the trigger is enabled.
Tab. 5-164:
Cleaning operation and trigger condition
Y215
STF
Time
Output frequency
ON
ON
Pr. 1474
0 Hz
As reverse rotation is disabled (Pr. 78 = "1"), forward
rotation is performed.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......