Parameters
(G) Control parameters
FR-F800
5 - 535
5.13.1 Manual
torque
boost
Voltage drop in the low-frequency range can be compensated, improving reduction of the motor
torque in the low-speed range.
●
Motor torque in the low-frequency range can be adjusted according to the load, increasing the
motor torque at the start up.
●
By using the RT signal, it is possible to switch between 2 types of torque boost.
Initial value for the FR-F820-00046(0.75K) or lower and FR-F840-00023(0.75K or lower.
Initial values for the FR-F820-00077(1.5K) to FR-F820-00167(3.7K), FR-F840-00038(1.5K) to
FR-F840-00083(3.7K).
Initial values for the FR-F820-00250(5.5K), FR-F820-00340(7.5K), FR-F840-00126(5.5K),
FR-F840-00170(7.5K).
Initial values for the FR-F820-00490(11K) to FR-F820-01540(37K), FR-F840-00250(11K) to FR-F840-
00770(37K).
!
Initial value for the FR-F820-01870(45K), FR-F820-02330(55K), FR-F840-00930(45K), FR-F840-
01160(55K).
Initial value for the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
Starting torque adjustment
●
Assuming Pr. 19 "Base frequency voltage" is 100%, set the output voltage at 0 Hz to Pr. 0 (Pr. 46)
in percentage.
●
Perform the adjustment of the parameter little by little (approximately 0.5%), and confirm the
status of the motor each time. The motor may overheat when the value is set too high. Do not use
more than 10% as a guideline.
Pr.
Name
Initial
value
Setting
range
Description
0
G000
Torque boost
0 to 30%
Set the output voltage at 0 Hz in %.
1.5%
46
G010
Second torque boost
9999
0 to 30%
Set the torque boost value at when RT signal is ON.
9999
Without second torque boost
Fig. 5-259:
Relationship between output frequency and
output voltage
I002748E
V/F
V/F
V/F
0
100%
Output
voltage
Setting
range
Output
frequency
(Hz)
Base
frequency
Pr. 0
Pr. 46
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......