(M) Monitor display and monitor output signal
Parameters
5 - 240
Input MC shutoff signal (Y91)
●
The Fault output 3 (Y91) signal is output when a fault originating in the inverter circuit or a
connection fault occurs.
●
To use the Y91 signal, set "91 (positive logic) or 191 (negative logic)" in any of Pr. 190 to Pr. 196
(output terminal function selection) to assign the function to the output terminal.
●
The following table shows the faults that output the Y91 signal. (For the fault details, refer to page 6-9.)
5.8.7 Output
frequency
detection
The inverter output frequency is detected and output as output signals.
Fault record
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
CPU fault (E.6)
CPU fault (E.7)
Parameter storage device fault (E.PE)
Parameter storage device fault (E.PE2)
24 V DC power fault (E.P24)
Operation panel power supply short circuit
RS-485 terminal power supply short circuit (E.CTE)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Brake transistor alarm detection (E.BE)
Internal circuit fault(E.13/E.PBT)
Tab. 5-104:
Faults that lead to Y91 signal output
Parameters referred to
Pr. 13
Starting frequency
=>
Pr. 76
Fault code output selection
=>
Pr.
Name
Initial value
Setting range Description
FM
CA
41
M441
Up-to-frequency
sensitivity
10%
0 to 100%
Set the level where the SU signal turns ON.
42
M442
Output frequency
detection
6 Hz
0 to 590 Hz
Set the frequency where the FU (FB) signal turns
ON.
43
M443
Output frequency
detection for reverse
rotation
9999
0 to 590 Hz
Set the frequency where the FU (FB) signal turns
ON in reverse rotation.
9999
Same as the Pr. 42 setting.
50
M444
Second output frequency
detection
30 Hz
0 to 590 Hz
Set the frequency where the FU2 (FB2) signal
turns ON.
870
M400
Speed detection
hysteresis
0 Hz
0 to 5 Hz
Set the hysteresis width for the detected
frequency.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......