Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 253
5.8.13
Pulse train output of output power
After power ON or inverter reset, output signal (Y79 signal) is output in pulses every time accumulated
output power, which is counted after the Pr. 799 "Pulse increment setting for output power" is set,
reaches the specified value (or its integral multiples).
Pulse increment setting for output power (Y79 signal, Pr. 799)
●
After power ON or inverter reset, output signal (Y79 signal) is output in pulses every time
accumulated output power of the inverter exceeds Pr. 799 "Pulse increment setting for output
power".
●
The inverter continues to count the output power at retry function or when automatic restart after
instantaneous power failure function works without power OFF of output power (power failure
that is too short to cause an inverter reset), and it does not reset the count.
●
If power failure occurs, output power is counted from 0 kWh again.
●
Assign pulse output of output power (Y79: setting value 79 (positive logic), 179 (negative logic))
to any of Pr. 190 to Pr. 196 (Output terminal function selection).
Pr.
Name
Initial value
Setting range
Description
799
M520
Pulse increment setting for
output power
1 kWh
0.1 kWh, 1 kWh,
10 kWh,
100 kWh,
1000 kWh
Pulse train output of output power (Y79)
is output in pulses at every output power
(kWh) that is specified.
I002834E
Fig. 5-110:
Pulse train output of output power
NOTES
Because the accumulated data in the inverter is cleared when control power is lost by power fail-
ure or at an inverter reset, the value on the monitor cannot be used to charge electricity bill.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
(Refer to page 5-231.)
In an application where the pulse outputs are frequently turned ON/OFF, do not assign the signal
to the terminal ABC1 or ABC2.
Otherwise, the life of the relay contact decreases.
Parameters referred to
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Output power
20 kWh
10 kWh
Pulse output of
output power
(Y79)
OFF
ON for 0.15 s
When Pr. 799 = 10
Time
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......