IP Office Installation
Page 66
15-601042 Issue 20b (16 July 2009)
IP Office
3.2 Environmental Requirements
The planned location must meet the following requirements. If being installed into a rack system, these are requirements
for within the rack:
1.
o
Temperature: 0°C to 40°C / 32°F to 104°F.
2.
o
Humidity: 10% to 95% non-condensing.
3.
o
Check there are no flammable materials in the area.
4.
o
Check there is no possibility of flooding.
5.
o
Check that no other machinery or equipment needs to be moved first.
6.
o
Check that it is not an excessively dusty atmosphere.
7.
o
Check that the area is unlikely to suffer rapid changes in temperature and humidity.
8.
o
Check for the proximity of strong magnetic fields, sources of radio frequency and other electrical interference.
9.
o
Check there are no corrosive chemicals or gasses.
10.
o
Check there is no excessive vibration or potential of excessive vibration, especially of any mounting surface.
11.
o
Check that where telephones are installed in another building, that the appropriate protectors and protective
grounds are fitted (see
Out of Building Telephone Installation
).
12.
o
Check there is suitable lighting for installation, system programming and future maintenance.
13.
o
Check that there is sufficient working space for installation and future maintenance.
14.
o
Ensure that likely activities near the system will not cause any problems, e.g. access to and maintenance of any
other equipment in the area.
15.
o
Where ventilation holes are present on any of the IP Office units, those holes should not be covered or blocked.
16.
o
The surface must be flat horizontal for free-standing or rack mounted installations.
Wall Mounting
In additional to the requirements above, the following are applicable to IP Office units that support wall mounting.
1. Units must only be mounted onto permanent wall surfaces.
2. The surface must be vertical and flat.
3. Orientation of the unit must be as shown in the sections on
IP500 Wall Mounting
or Small Office Edition Wall Mounting.
4. The appropriate Avaya wall mounting kits must be used.
IMPORTANT SAFETY INSTRUCTIONS
When using your telephone equipment, basic safety precautions should always be followed to reduce the risk of fire,
electric shock and injury to persons, including the following:
1. Do not use this product near water, for example, near a bath tub, wash bowl, kitchen sink or laundry tub, in a wet
basement or near a swimming pool.
2. Avoid using a telephone (other than a cordless type) during an electrical storm. There may be a remote risk of electric
shock from lightning.
3. Do not use the telephone to report a gas leak in the vicinity of the leak.
4. Use only the power cord and batteries indicated in this manual. Do not dispose of batteries in a fire. They may explode.
Check with local codes for possible special disposal instructions.
Summary of Contents for IP Office Phone Manager
Page 2: ...15 601042 Issue 20b 16 July 2009 IP Office Installation IP Office ...
Page 7: ......
Page 9: ......
Page 63: ......
Page 64: ...IP Office Installation Page 63 15 601042 Issue 20b 16 July 2009 IP Office Planning Chapter 3 ...
Page 69: ...IP Office Installation Page 68 15 601042 Issue 20b 16 July 2009 IP Office ...
Page 75: ......
Page 109: ......
Page 141: ......
Page 157: ...IP Office Installation Page 156 15 601042 Issue 20b 16 July 2009 IP Office ...
Page 165: ...IP Office Installation Page 164 15 601042 Issue 20b 16 July 2009 IP Office ...
Page 197: ...IP Office Installation Page 196 15 601042 Issue 20b 16 July 2009 IP Office ...
Page 391: ......
Page 409: ......
Page 410: ...IP Office Installation Page 409 15 601042 Issue 20b 16 July 2009 IP Office ...