(T) Multi-Function Input Terminal Parameters
Parameters
5 - 280
Input terminal function assignment
●
Using Pr. 178 to Pr. 189, set the functions of the input terminals
●
Refer to the following table and set the parameters.
Setting
Signal
name
Function
Related parameter
Refer to
page
0
RL
Pr. 59 = 0 (initial
value)
Low-speed operation
command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
≠
Remote setting (setting clear)
Pr. 59
1
RM
Pr. 59 = 0 (initial
value)
Middle-speed operation
command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
≠
Remote setting (deceleration)
Pr. 59
2
RH
Pr. 59 = 0 (initial
value)
High-speed operation
command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
≠
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44 to Pr. 51, Pr. 450 to Pr. 463,
Pr. 569, Pr. 832, etc.
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
6
CS
Selection of automatic restart after instantaneous
power failure, flying start
Pr. 57, Pr. 58, Pr. 162 to Pr. 165,
Pr. 299, Pr. 611
Electronic bypass function
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
7
OH
External thermal relay input
Pr. 9
8
REX
15-speed selection
(Combination with multi-speeds of RL, RM, and RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
10
X10
Inverter run enable signal (FR-HC2/FR-CV/FR-CC2
connection)
Pr. 30, Pr. 599
11
X11
FR-HC2/FR-CC2 connection, instantaneous power
failure detection
Pr. 30
12
X12
PU operation external interlock
Pr. 79
13
X13
External DC injection brake operation start
Pr. 10 to Pr. 12
14
X14
PID control valid terminal
Pr. 127 to Pr. 134, Pr. 575 to
Pr. 577
16
X16
PU/External operation switchover
(External operation with X16-ON)
Pr. 79, Pr. 340
18
X18
V/F switchover (V/F control with X18-ON)
Pr. 80, Pr. 81, Pr. 800
24
MRS
Output stop
Pr. 17
Electronic bypass function
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
25
STP
(STOP)
Start self-holding selection
Pr. 250
28
X28
Start-time tuning start external input
Pr. 95
37
X37
Traverse function selection
Pr. 592 to Pr. 597
38
PDI1
PID multistage set point setting 1
Pr. 1460 to Pr. 1466
39
PDI2
PID multistage set point setting 2
40
PDI3
PID multistage set point setting 3
46
TRG
Trace trigger input
Pr. 1020 to Pr. 1047
47
TRC
Trace sampling start/end
Pr. 1020 to Pr. 1047
48
X48
Power failure stop external
Pr. 261 to Pr. 266, Pr. 294, Pr. 668
50
SQ
Sequence start
Pr. 414
51
X51
Fault clear
Pr. 414
60
STF
Forward rotation command
(Assignable to the STF terminal (Pr. 178) only)
Pr. 250
61
STR
Reverse rotation command
(Assignable to the STR terminal (Pr. 179) only)
Pr. 250
62
RES
Inverter reset
Pr. 75
64
X64
During retry
Pr. 127 to Pr. 134
Tab. 5-126:
Input terminal function assignment (1)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......