Protective functions
Causes and corrective actions
FR-F800
6 - 13
6.5.2 Warning
Output is not shut off when a protective function activates.
Operation panel
indication
OL
FR-LU08
OL
Name
Stall prevention (overcurrent)
Description
When the output current of the inverter increases, the stall prevention (overcurrent)
function activates.
The following section explains about the stall prevention (overcurrent) function.
During
acceleration
When the output current of the inverter exceeds the stall prevention
level (Pr. 22 "Stall prevention operation level", etc.), this function stops
the increase in frequency until the overload current decreases to
prevent the inverter from resulting in overcurrent trip. When the
overload current has reduced below stall prevention operation level,
this function increases the frequency again.
During
constant-speed
operation
When the output current of the inverter exceeds the stall prevention
level (Pr. 22 "Stall prevention operation level", etc.), this function reduces
frequency until the overload current decreases to prevent the inverter
from resulting in overcurrent trip. When the overload current has
reduced below stall prevention operation level, this function increases
the frequency up to the set value.
During
deceleration
When the output current of the inverter exceeds the stall prevention
level (Pr. 22 "Stall prevention operation level", etc.), this function stops
the decrease in frequency until the overload current decreases to
prevent the inverter from resulting in overcurrent trip. When the
overload current has decreased below stall prevention operation level,
this function decreases the frequency again.
Check point
Check that the Pr. 0 "Torque boost" setting is not too large.
The Pr. 7 "Acceleration time" and Pr. 8 "Deceleration time" settings may be too short.
Check that the load is not too heavy.
Check for any failures in peripheral devices.
Check that the Pr. 13 "Starting frequency" is not too large.
Check that Pr. 22 "Stall prevention operation level" is appropriate.
Corrective action
Gradually increase or decrease the Pr. 0 setting by 1% at a time and check the motor
status.(Refer to page 5-515.)
Set a larger value in Pr. 7 "Acceleration time" and Pr. 8 "Deceleration time".
(Refer to page 5-99.)
Reduce the load.
Try Advanced magnetic flux vector control.
Change the Pr. 14 "Load pattern selection" setting.
The stall prevention operation current can be set in Pr. 22 "Stall prevention operation level".
The acceleration/deceleration time may change. Increase the stall prevention operation
level with Pr. 22 "Stall prevention operation level", or disable stall prevention with Pr. 156
"Stall prevention operation selection". (Use Pr. 156 to set either operation continued or not
at OL operation.)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......