Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 193
5.8.2
Monitor indicator selection using operation panel or via communication
The monitored item to be displayed on the operation panel or the parameter unit can be selected.
Pr.
Name
Initial value
Setting range
Description
52
M100
Operation panel main
monitor selection
0
(output
frequency)
0, 5 to 14, 17, 18, 20,
23 to 25, 34, 38, 40
to 45, 50 to 57, 61,
62, 64, 67 to 69, 81
to 96, 98, 100
Select the monitor to be displayed on the
operation panel and the parameter unit.
Refer to page 5-194 for the monitor
description.
774
M101
Operation panel monitor
selection 1
9999
1 to 3, 5 to 14,
17, 18, 20, 23 to 25,
34, 38, 40 to 45, 50
to 57, 61, 62, 64, 67
to 69, 81 to 96, 98,
100, 9999
The output frequency, output current and
output voltage monitor that are displayed in
monitor mode on the operation panel and the
parameter unit can be switched to a specified
monitor.
9999: Follows the Pr. 52 setting.
775
M102
Operation panel monitor
selection 2
776
M103
Operation panel monitor
selection 3
992
M104
Operation panel setting
dial push monitor
selection
0
(Set
frequency)
0 to 3, 5 to 14,
17, 18, 20, 23 to 25,
34, 38, 40 to 45, 50
to 57, 61, 62, 64, 67
to 69, 81 to 96, 98,
100
Select the monitor to be displayed when the
setting dial on the operation panel is pushed.
170
M020
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter monitor.
10
Set the maximum value for monitoring via
communication. Set it in the range of 0 and
9999 kWh.
9999
Set the maximum value for monitoring via
communication. Set it in the range of 0 and
65535 kWh.
563
M021
Energization time
carrying-over times
0
(0 to 65535)
(Read-only)
Displays the numbers of times that the
cumulative energization time monitor
exceeded 65535 h. Read-only.
268
M022
Monitor decimal digits
selection
9999
0
Displays as integral value.
1
Displays in 0.1 increments.
9999
No function
891
M023
Cumulative power monitor
digit shifted times
9999
0 to 4
Set the number of times to shift the
cumulative power monitor digit.
The monitor value is clamped at the
maximum value.
9999
No shift
Monitor value is cleared when it exceeds the
maximum value.
171
M030
Operation hour meter
clear
9999
0
Set "0" to clear the operation hour monitor.
9999
The read value is always 9999. Nothing
happens when "9999" is set.
564
M031
Operating time carrying-
over times
0
(0 to 65535)
(Read-only)
Displays the numbers of times that the
operating time monitor exceeded 65535 h.
Read-only.
290
M044
Monitor negative output
selection
0
0 to 7
Set the availability of output with a minus sign
for the terminal AM, the operation panel
display, or monitoring via communication.
(Refer to page 5-204.)
1018
M045
Monitor with sign
selection
9999
0
Select items to be displayed with minus signs.
9999
1106
M050
Torque monitor filter
9999
0 to 5 s
The filter time constant is selectable for
monitoring of the torque. A larger setting
results in slower response.
9999
0.3 s filter
1107
M051
Running speed monitor
filter
9999
0 to 5 s
The filter time constant is selectable for
monitoring of the running speed. A larger
setting results in slower response.
9999
0.08 s filter
1108
M052
Excitation current monitor
filter
9999
0 to 5 s
The filter time constant is selectable for
monitoring of the motor excitation current. A
larger setting results in slower response.
9999
0.3 s filter
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......