(T) Multi-Function Input Terminal Parameters
Parameters
5 - 252
To run with an analog input voltage
●
Concerning the frequency setting signal, input 0 to 5 V DC (or 0 to 10 V DC) to terminals 2 and 5.
The 5 V (10 V) input is the maximum output frequency.
●
The power supply 5 V (10 V) can be input by either using the internal power supply or preparing
an external power supply. The internal power source is 5 V DC output between terminals 10 and
5, and 10 V DC output between terminals 10E and 5.
●
To supply the 10 V DC input to terminal 2, set "0, 2, 4, 10, 12, or 14" in Pr. 73. (The initial value is 0
to 5 V.)
●
Setting "1 (0 to 5 V DC)" or "2 (0 to 10 V DC)" in Pr. 267 and turning the voltage/current input
switches OFF sets the terminal 4 to the voltage input specification. Turning ON the AU signal
activates terminal 4 input.
Terminal
Inverter internal power
source voltage
Frequency
setting resolution
Pr. 73
(terminal 2 input voltage)
10
5 V DC
0.030 Hz/60 Hz
0 to 5 V DC input
10E
10 V DC
0.015 Hz/60 Hz
0 to 10 V DC input
Tab. 5-111:
Built-in power supply voltage
Fig. 5-112:
Frequency setting by voltage 0 to 5V DC
I002638E
Fig. 5-113:
Frequency setting by voltage 0 to 10 V DC
I002639E
Fig. 5-114:
Frequency setting by voltage 0 to 5V DC
I002640E
NOTE
The wiring length of the terminal 10, 2, 5 should be 30 m at maximum.
STF
SD
10
2
5
2
4
0 to 5 V DC
Voltage/current
input switch
Frequency
setting
Connection diagram using
terminal 2 (0 to 5 V DC)
Forward
rotation
Inverter
STF
SD
10E
2
5
2
4
Forward
rotation
0 to 10 V DC
Frequency
setting
Inverter
Voltage/current
input switch
Connection diagram using
terminal 2 (0 to 10 V DC)
STF
SD
AU
10
4
5
2
4
Inverter
Voltage/current
input switch
Forward
rotation
Terminal 4
input selection
0 to 5 V DC
Frequency
setting
Connection diagram using
terminal 4 (0 to 5 V DC)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......