Power supply harmonics
Precautions for use of the inverter
3 - 12
3.2.2
Harmonic suppression guidelines
Inverters have a converter section (rectifier circuit) and generate a harmonic current.
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The Har-
monic Suppression Guidelines was established to protect other consumers from these outgoing har-
monic currents.
The three-phase 200 V input specifications 3.7 kW or lower were previously covered by "the Harmonic
Suppression Guidelines for Household Appliances and General-purpose Products" and other models
were covered by "the Harmonic Suppression Guidelines for Consumers Who Receive High Voltage or
Special High Voltage". However, the transistorized inverter has been excluded from the target prod-
ucts covered by "the Harmonic Suppression Guidelines for Household Appliances and General-pur-
pose Products" in January 2004 and "the Harmonic Suppression Guideline for Household Appliances
and General-purpose Products" was repealed on September 6, 2004.
All capacity and all models of general-purpose inverter used by specific consumers are now covered
by "the Harmonic Suppression Guidelines for Consumers Who Receive High Voltage or Special High
Voltage" (hereinafter referred to as "the Specific Consumer Guidelines").
"Specific Consumer Guidelines"
This guideline sets forth the maximum harmonic currents outgoing from a high-voltage or especially
high-voltage receiving consumer who will install, add or renew harmonic generating equipment. If
any of the maximum values is exceeded, this guideline requires that consumer to take certain sup-
pression measures.
Application of the specific consumer guidelines
Received power
voltage
5th
7th
11th
13th
17th
19th
23rd
Over 23rd
6.6 kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22 kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33 kV
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
Tab. 3-7:
Maximum values of outgoing harmonic currents per 1 kW contract power
I002422E
Fig. 3-10:
Application of the specific consumer guidelines
Install, add or renew
equipment
Calculation of equivalent
capacity total
Equivalent
capacity total
Calculation of outgoing
harmonic current
Not
more than
harmonic current
upper limit?
Harmonic suppression
measures necessary
Harmonic suppression
measures unnecessary
Equal to or less
than reference
capacity
Above reference
capacity
More than upper limit
Equal to or less
than upper
limit
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......