Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 229
79
179
Y79
Pulse train output of
output power
Output in pulses every time the
accumulated output power of the
inverter reaches the Pr. 799 setting.
Pr. 799
82
182
Y82
BACnet binary output
Enables output from the Binary Output
object for BACnet communication.
Pr. 549
85
185
Y85
DC current feeding
Output when there is a power failure or
undervoltage for the AC current.
Pr. 30
86
186
Y86
Control circuit capacitor
life
(for Pr. 313 to Pr. 322)
Output when the control circuit capacitor
approaches the end of its life.
Pr. 255 to
Pr. 259
87
187
Y87
Main circuit capacitor life
(for Pr. 313 to Pr. 322)
Output when the main circuit capacitor
approaches the end of its life.
88
188
Y88
Cooling fan life
(for Pr. 313 to Pr. 322)
Output when the cooling fan approaches
the end of its life.
89
189
Y89
Inrush current limit circuit
life
(for Pr. 313 to Pr. 322)
Output when the inrush current limit
circuit approaches the end of its life.
90
190
Y90
Life alarm
Output when any of the control circuit
capacitor, main circuit capacitor and
inrush current limit circuit or the cooling
fan approaches the end of its life.
91
191
Y91
Fault output 3(power-OFF
signal)
Output when an error occurs due to an
inverter circuit fault or connection fault.
⎯
92
192
Y92
Energy saving average
value updated timing
Switches between ON and OFF each time
the average power saving is updated
when using the power saving monitor.
This cannot be set in Pr. 195 or Pr. 196,Pr.
320 to Pr. 322 (relay output terminal).
Pr. 52, Pr. 54,
Pr. 158,
Pr. 891 to
Pr. 899
93
193
Y93
Current average monitor
signal
Outputs the average current and
maintenance timer value as a pulse.
This cannot be set in Pr. 195 or Pr. 196,
Pr. 320 to Pr. 322 (relay output terminal).
Pr. 555 to
Pr. 557
94
194
ALM2
Fault output 2
Output when the inverter's protective
function is activated to stop the output
(at fault occurrence).
The signal output continues even during
an inverter reset, and the signal output
stops after the reset release.
⎯
95
195
Y95
Maintenance timer signal
Output when Pr. 503 reaches the Pr. 504
setting or higher.
Pr. 503, Pr. 504
96
196
REM
Remote output
Output via terminals when certain
parameters are set.
Pr. 495 to
Pr. 497
98
198
LF
Alarm
Output when an alarm (fan fault or
communication error warning) occurs.
Pr. 121, Pr. 244
99
199
ALM
Fault
Output when the inverter's protective
function is activated to stop the output
(at fault occurrence). The signal output is
stopped after a reset.
⎯
200
300
FDN2
Second PID lower limit
Output when the value is lower than the
lower limit of second PID control.
Pr. 753 to
Pr. 758
201
301
FUP2
Second PID upper limit
Output when the value is higher than the
upper limit of second PID control.
202
302
RL2
Second PID forward/
reverse rotation output
Output during forward rotation under
second PID control.
203
303
PID2
Second During PID
control activated
Output during second PID control.
204
304
SLEEP2
During second PID
output shutoff
Output during second PID output
suspension function operation.
Pr. 753 to
Pr. 758, Pr. 1147
to Pr. 1149
205
305
Y205
Second PID deviation
limit
Output when the absolute deviation
value during second PID control exceeds
the limit value.
Pr. 753 to
Pr. 758,
Pr. 1145,
Pr. 1146
Setting
Signal
name
Function
Operation
Related
parameter
Refer to
page
Positive
logic
Negative
logic
Tab. 5-101:
Output terminal function assignment (3)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......