(G) Control parameters
Parameters
5 - 546
5.13.13 Slip
compensation
Slip of the motor is estimated from the inverter output current at the time of V/F control, and maintain
the rotation of the motor constant.
●
Slip compensation will become enabled by calculating the rated motor slip, and setting to Pr. 245.
Slip compensation is not performed when Pr. 245 = "0, 9999".
5.13.14 Speed
smoothing
control
There are times where the vibration due to mechanical resonance affect the inverter, making the out-
put current (torque) unstable. In such case, vibration can be decreased by reducing the deviation in
the output current (torque) by changing the output frequency.
Pr.
Name
Initial
value
Setting
range
Description
245
G203
Rated slip
9999
0.01 to 50%
Set the rated motor slip.
0, 9999
Without slip compensation
246
G204
Slip compensation time
constant
0.5s
0.01 to 10s
Set the response time of the slip compensation.
Response will become faster when the value is
lowered, but the regenerative overvoltage (E.OV[])
error will occur more frequently when the load inertia
is larger.
247
G205
Constant-power range slip
compensation selection
9999
0
Do not perform slip compensation at constant output
range (frequency range higher than the frequency set
in Pr. 3).
9999
Perform the slip compensation of the constant
output range.
Rated slip
=
Synchronized speed at the time of base frequency - rated rotation speed
× 100[%]
Synchronized speed at the time of base frequency
NOTES
When the slip compensation is performed, the output frequency may become larger than the set
frequency. Set Pr. 1 "Maximum frequency" higher than the set frequency.
Slip compensation will be disabled in following cases.
At the times of stall preventive (oL, OL) operation, regeneration avoidance operation, auto tuning.
Parameters referred to
Pr. 1
Maximum frequency
=>
Pr. 3
Base frequency
=>
Pr.
Name
Initial
value
Setting
range
Description
653
G410
Speed smoothing control
0%
0 to 200%
Confirm the effect by raising and lowering the value
with 100% as a reference.
654
G411
Speed smoothing cutoff
frequency
20 Hz
0 to 120 Hz
Set the lower limit of the torque deviation cycle
(frequency).
V/F
V/F
V/F
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......