(M) Monitor display and monitor output signal
Parameters
5 - 226
5.8.6 Output
terminal
function selection
Use the following parameters to change the functions of the open collector output terminals and re-
lay output terminals.
The initial value is for standard models.
The initial value is for separated converter types.
Parameters referred to
Pr. 3
Base frequency
=>
Pr. 52
Operation panel main monitor selection
=>
Pr. 54
FM/CA terminal function selection
=>
Pr. 158
AM terminal function selection
=>
Pr.
Name
Initial
value
Initial set signal
Setting range
190
M400
RUN terminal function
selection
Open
collec-
tor
output
terminal
0
RUN (Inverter running)
0 to 5, 7, 8, 10 to 19, 25, 26, 35, 39 to
42, 45 to 54, 57, 64 to 68, 70 to 79,
82, 85, 90 to 96, 98 to 105, 107, 108,
110 to 116, 125, 126, 135, 139 to
142, 145 to 154, 157, 164 to 168,
170 to 179, 182, 185, 190 to 196,
198 to 208, 211 to 213, 215, 217 to
220, 226, 228 to 230, 300 to 308,
311 to 313, 315, 317 to 320, 326,
328 to 330
191
M401
SU terminal function
selection
1
SU (Up to frequency)
192
M402
IPF terminal function
selection
2
IPF (Instantaneous
power failure/
undervoltage)
9999
193
M403
OL terminal function
selection
3
OL (Overload warning)
194
M404
FU terminal function
selection
4
FU (Output frequency
detection)
195
M405
ABC1 terminal function
selection
Relay
output
terminal
99
ALM (Fault)
0 to 5, 7, 8, 10 to 19, 25, 26, 35, 39 to
42, 45 to 54, 57, 64 to 68, 70 to 79,
82, 85, 90, 91, 94 to 96, 98 to 105,
107, 108, 110 to 116, 125, 126, 135,
139 to 142, 145 to 154, 157, 164 to
168, 170 to 179, 182, 185, 190, 191,
194 to 196, 198 to 208, 211 to 213,
215, 217 to 220, 226, 228 to 230,
300 to 308, 311 to 313, 315, 317 to
320, 326, 328 to 330
196
M406
ABC2 terminal function
selection
9999
No function
Pr.
Name
Initial
value
Setting range
Description
289
M431
Inverter output terminal
filter
9999
5 to 50 ms
Set the time delay for the output terminal
response.
9999
No output terminal filter.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......