(G) Control parameters
Parameters
5 - 530
5.13.9 Stop
selection
Select the stopping method (deceleration to stop or casting) at turn-OFF of the start signal.
Use this function to stop a motor with a mechanical brake at turn-OFF of the start signal.
Selection of start signal (STF/STR) operation can also be selected. (For start signal selection, refer to
page 5-287.)
Make the motor perform deceleration stop
●
Set Pr. 250 = "9999 (initial value) or 8888".
●
It will perform deceleration stop when the start signal (STF/STR) is turned OFF.
Parameters referred to
Pr. 10
DC injection brake operation frequency
=>
Pr. 11
DC injection brake operation time
=>
Pr. 12
DC injection brake operation voltage
=>
Pr. 13
Starting frequency
=>
Pr.
Name
Initial
value
Setting
range
Description
Start signal (STF/STR)
(Refer to page 5-287.)
Stop operation
250
G106
Stop selection
9999
0 to 100 s
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
It will coast to stop after
set time when the start
signal is turned OFF.
1000 s to
1100 s
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
It will coast to stop after
(Pr. 250 – 1000) s when the
start signal is turned OFF.
9999
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
It will perform
deceleration stop when
the start signal is turned
OFF.
8888
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
I001143E
Fig. 5-255:
Stop operation when parameter 250 = 8888 or 9999
Output
frequency [Hz]
Start signal
DC brake
Deceleration starts when start signal turns off
Time
ON
ON
OFF
OFF
RUN signal
Deceleration time (Time set in Pr. 8, etc.)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......