Start signal operation selection
Operation of start signal (STF/STR) can be selected.
Select the stopping method (deceleration to stop or casting) at turn-OFF of the start signal.
Use this function to stop a motor with a mechanical brake at turn-OFF of the start signal.
2-wire type (STF, STR signal)
●
The following figure shows the connection in 2-wire type.
●
As an initial setting, forward/reverse rotation signals (STF/STR) acts as both start and stop signals.
Either one turned ON will be enabled, and the operation will follow that signal. The motor will
perform a deceleration stop when both are turned OFF (or both are turned ON) during the
operation.
●
There are methods such as inputting 0 to 10 V DC between the speed setting input terminals 2
and 5, or Pr. 4 to Pr. 6 (multi-speed setting (fast, medium, slow)) for the frequency setting signal.
(For multi-speed operation, refer to page 5-57.)
●
By setting Pr. 250 = "1000 to 1100, 8888", STF signal becomes start command and STF signal
becomes forward/reverse command.
Pr.
Name
Initial value
Setting range
Description
Start signal (STF/STR)
Stop operation
(Refer to page 5-287)
250
G106
Stop
selection
9999
0 to 100 s
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
Turn OFF the start signal and
it will coast to stop after the
specified time period.
When set to 1000 s to 1100 s,
it will coast to stop after
(Pr. 250 – 1000) s.
1000 s to 1100 s
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
9999
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
It will perform deceleration
stop when the start signal is
turned OFF.
8888
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
I002656E
Fig. 5-138:
2-wire type connection example (Pr. 250 = "9999")
STF
STF
STR
SD
STR
10
2
5
Forward
rotation start
Reverse
rotation start
Inverter
Time
Rev
e
rse
rotation
Fo
rw
a
rd
rotat
ion
Out
p
ut
fr
eque
nc
y
ON
ON
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......