(A) Application parameters
Parameters
5 - 388
I003051E
Fig. 5-185:
Flow control by auxiliary motors
NOTES
The motor 1 (M1) starts first when power is turned ON for the first time or after inverter reset.
When the Pr. 578 or Pr. 579 setting has been changed, the motor 1 (M1) starts first.
Q3
Q2
Q1
Time
Flow rate Q
Driven by
inverter
Driven by
commercial
power
supply
The starting order of motors is M2
→
M3
→
M1 if the previous order was M1
→
M2
→
M3.
The motor starts in the order of elapsed time after completion of the previous inverter-driven operation, from
the longest to the shortest. (The motor that has not been driven by the inverter for the longest time starts first.)
Qmax
Pr. 579 = 0
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
Pr. 579 = 1
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
Pr. 579 = 2
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)
Pr. 579 = 3
Motor 1 (M1)
Motor 2 (M2)
Motor 3 (M3)
Motor 4 (M4)