Causes and corrective actions
Protective functions
6 - 12
Operation panel
indication
rE6
Name
File error
Description
The parameter copy file in the USB memory device cannot be recognized.
An error has occurred in the file system during transfer of the PLC function data or writing to
RAM.
Check point
⎯
Corrective action
Perform parameter copy again.(Refer to page 5-553.)
Copy the PLC function project data again.(Refer to page 5-437.)
Operation panel
indication
rE7
Name
File quantity error
Description
A parameter copy was attempted to the USB memory device in which the copy files from
001 to 099 had already been saved.
Check point
Check if the number of copy files in the USB memory device has reached 99.
Corrective action
Delete the copy file in the USB memory device and perform parameter copy again.(Refer to
page 5-553.)
Operation panel
indication
rE8
Name
No PLC function project file
Description
The specified PLC function project file does not exist in the USB memory device.
Check point
Check that the file exists in the USB memory device.
Check that the folder name and the file name in the USB memory device is correct.
Corrective action
The data in the USB memory device may be damaged.
Operation panel
indication
Err.
Name
Error
Description
The RES signal is turned ON.
The operation panel and inverter cannot make normal communication (contact faults of the
connector).
This error may occur when the voltage at the input side of the inverter drops.
When using a separate power source for the control circuit power (R1/L11, S1/L21) from the
main circuit power (R/L1, S/L2, T/L3), this error may appear at turning ON of the main circuit.
It is not a fault.
Corrective action
Turn OFF the RES signal.
Check the connection between the operation panel and the inverter.
Check the voltage on the input side of the inverter.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......