Parameters
(A) Application parameters
FR-F800
5 - 411
●
For the terminal to be used for the X10 and X11 signal, set "10" (X10), "11" (X11) in Pr. 178 to Pr.
189 and assign the function. (For separated converter types, the X10 signal is assigned to the
terminal MRS in the initial setting.)
●
For the X10 signal of separated converter types, NC contact input specification is selected in the
initial setting. Set Pr. 599 = "0" to change the input specification to NO contact.
Fig. 5-206:
Connecting the signals X10, X11, CS
I002850E
NOTES
Changing the terminal assignment using Pr. 178 to Pr. 189 may affect other functions. Set param-
eters after confirming the function of each terminal.
If the CS signal is not assigned to any input terminal, solely setting Pr. 57 will enable the restart
operation at all times.
RDA
X10
IPF
X11
CS
SE
SD
Separated converter type
Converter unit
Inverter