Common specifications
Specifications
8 - 10
8.3 Common
specifications
C
o
ntr
o
l spe
cif
ica
tions
Control method
Soft-PWM control, high carrier frequency PWM control (selectable among V/F control (Optimum excitation
control), Advanced magnetic flux vector control (Advanced optimum excitation control) and PM motor control)
Output frequency range
0.2 to 590 Hz (up to 400 Hz under Advanced magnetic flux vector control, and PM motor control.)
Frequency
setting
resolution
Analog input
0.015 Hz/60 Hz (0 to 10 V/12 bits for terminals 2 and 4)
0.03 Hz/60 Hz (0 to 5 V/11 bits or 0 to 20 mA/
approx. 11 bits for terminals 2 and 4, 0 to ±10 V/12 bits for terminal 1)
0.06 Hz/60 Hz (0 to ±5 V/11 bits for terminal 1)
Digital input
0.01 Hz
Frequency
accuracy
Analog input
Within ±0.2% of the max. output frequency (25 °C ± 10 °C)
Digital input
Within 0.01% of the set output frequency
Voltage/frequency
characteristics
Base frequency can be set from 0 to 590 Hz.
Constant-torque/variable-torque pattern or adjustable 5 points V/F can be selected.
Starting
torque
"
Induction
motor
120% 0.5 Hz (Advanced magnetic flux vector control)
IPM motor
50%
Torque boost
Manual torque boost
Acceleration/deceleration
time setting
0 to 3600 s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration
mode, backlash countermeasures acceleration/deceleration can be selected.
DC injection brake
(induction motor)
Operation frequency (0 to 120 Hz), operation time (0 to 10 s), operation voltage (0 to 30%) variable
Stall prevention operation
level
Activation range of stall prevention operation (SLD rating: 0 to 120%, LD rating: 0 to 150%
)
. Whether to use the
stall prevention or not can be selected (V/F control, Advanced magnetic flux vector control)
Oper
a
tio
n
spec
if
ic
a
tion
s
Frequency
setting
signal
Analog input
Terminals 2 and 4: 0 to 5 V, 0 to 10 V, 4 to 20 mA (0 to 20 mA) are available.
Terminal 1: -5 to +5 V, -10 to +10 V are available.
Digital input
Input using the setting dial of the operation panel or the parameter unit
Four-digit BCD or 16-bit binary (when used with option FR-A8AX)
Start signal
Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.
Input signals
(twelve terminals)
Low-speed operation command, Middle-speed operation command, High-speed operation command,
Second function selection, Terminal 4 input selection, Jog operation selection, Output stop, Start self-holding
selection, Forward rotation command, Reverse rotation command, Inverter reset.
The input signal can be changed using Pr. 178 to Pr. 189 (input terminal function selection).
Pulse train input
100 kpps
Operational functions
Maximum and minimum frequency settings, multi-speed operation, acceleration/deceleration pattern,
thermal protection, DC injection brake, starting frequency, JOG operation, output stop (MRS), stall prevention,
regeneration avoidance, increased magnetic excitation deceleration, DC feeding
, frequency jump, rotation
display, automatic restart after instantaneous power failure, electronic bypass sequence, remote setting, retry
function, carrier frequency selection, fast-response current limit, forward/reverse rotation prevention,
operation mode selection, slip compensation, speed smoothing control, traverse, auto tuning, applied motor
selection, RS-485 communication, PID control, PID pre-charge function, cooling fan operation selection, stop
selection (deceleration stop/coasting), power-failure deceleration stop function, PLC function, life diagnosis,
maintenance timer, current average monitor, multiple rating, test run, 24 V power supply input for control
circuit, safety stop function, self power management, BACnet communication, PID gain tuning, cleaning, load
characteristics storage, emergency drive
Output signal
Open collector output (five
terminals)
Relay output
(two terminals)
Inverter running, Up to frequency, Instantaneous power failure/undervoltage
, Overload warning,
Output frequency detection, Fault
The output signal can be changed using Pr.190 to Pr.196 (output terminal function selection).
Fault codes of the inverter can be output (4 bits) from the open collector.
Pulse train output
50 kpps
Tab. 8-7:
Common specifications (1)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......