(T) Multi-Function Input Terminal Parameters
Parameters
5 - 258
5.9.4 Analog
input
responsiveness and noise elimination
The frequency command responsiveness and stability are adjustable by using the analog input (ter-
minals 1, 2, and 4) signal.
Block diagram
Pr.
Name
Initial value
Setting range
Description
74
T002
Input filter time constant
1
0 to 8
The primary delay filter time
constant to the analog input is
selectable. The higher the value, the
lower the responsiveness.
822
T003
Speed setting filter 1
9999
0 to 5 s
Set the primary delay filter time
constant to the external speed
command (analog input command).
9999
Use the Pr. 74 setting.
832
T005
Speed setting filter 2
9999
0 to 5 s, 9999
Second function of Pr. 822 (enabled
when the RT signal is ON)
849
T007
Analog input offset adjustment
100%
0 to 200%
Make the analog speed input
(terminal 2) have an offset. This
prevents the motor from rotating by
noise to the analog input or another
cause on the speed 0 command.
I003086E
Fig. 5-122:
Terminal 1 (2, 4) input block diagram
Speed command
Pr. 74
Pr. 822
Pr. 832
Pr. 822 = 9999
Pr. 822
≠
9999
Pr. 832 = 9999
Pr. 832
≠
9999
RT-OFF
RT-ON
Terminal 1 (2, 4) input
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......