(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Parameters
5 - 114
5.5.5
Minimum motor speed frequency
Set the frequency where the PM motor starts running.
Set the deadband in the low-speed range to eliminate noise and offset deviation when setting a fre-
quency with analog input.
Starting frequency setting (Pr. 13)
●
The frequency where the PM motor starts running can be set in the range of 0 to 60 Hz.
●
While the frequency command is less than the Pr. 13 "Starting frequency" setting, the PM motor
is stopped.
When the frequency command reaches the set frequency or higher, the PM motor accelerates
according to the Pr. 7 "Acceleration time" setting.
Pr.
Name
Initial value
Setting range
Description
13
F102
Starting frequency
Minimum
frequency/
Minimum
rotations per
minute
0 to 60 Hz
Set the frequency where the motor
starts running.
Fig. 5-30:
Starting frequency parameter
I002568E
NOTES
Under induction motor control (under V/F control and Advanced magnetic flux vector control),
the output starts at the frequency set in Pr. 13. Under PM motor control, the output always starts
at 0.01 Hz.
The inverter output does not start when the frequency-setting signal is less than Pr. 13. For exam-
ple, while Pr. 13 = "20 Hz", the inverter output starts when the frequency setting signal reaches
20 Hz.
E
CAUTION:
Note that when Pr. 13 is set to any value equal to or lower than the setting of Pr. 2 "Minimum
frequency", simply turning ON the start signal will run the motor at the frequency set in Pr. 2
even if the command frequency is not input.
Parameters referred to
Pr. 2
Minimum frequency
=>
Pr. 7
Acceleration time
=>
PM
PM
PM
60
0
Output
frequency
(Hz)
Setting r
a
nge
Set frequency
Output
frequency
Time
Output from 0.01 Hz
STF
ON
Pr. 13
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......