Parameters
(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
FR-F800
5 - 101
Deceleration time setting (Pr. 8, Pr. 20)
●
Use Pr. 8 "Deceleration time" to set the deceleration time required to reach a stop status from to
Pr. 20 "Acceleration/deceleration reference frequency".
●
Set the deceleration time according to the following formula.
Changing the minimum increment of the acceleration/deceleration time (Pr. 21)
●
Use Pr. 21 to set the minimum increment of the acceleration/deceleration time.
–
Setting value "0" (initial value): minimum increment 0.1 s
–
Setting value "1": minimum increment 0.01 s
●
Pr. 21 setting allows the minimum increment of the following parameters to be changed:
Pr. 7, Pr. 8, Pr. 16, Pr. 44, Pr. 45, Pr. 111, Pr. 264, Pr. 265, Pr. 582, Pr. 583, Pr. 791, Pr. 792, Pr. 1477, Pr. 1478
Deceleration time setting
=
Pr. 20
×
Deceleration time from maximum frequency to stop
(Maximum frequency – Pr. 10)
Example
쑴
For example, the following calculation is used to find the setting value for Pr. 8 when increasing the
output frequency to the maximum frequency of 50 Hz in 10 s with Pr. 20 = 120 Hz and Pr. 10 = 3 Hz.
Pr. 8 = 120 Hz × 10 s / (50 Hz - 3 Hz)
≈
25.5 s
쑶
NOTES
If the acceleration/deceleration time is set, the actual motor acceleration/deceleration time can-
not be made shorter than the shortest acceleration/deceleration time determined by the mechan-
ical system J (moment of inertia) and motor torque.
If the Pr. 20 setting is changed, the Pr. 125 and Pr. 126 (frequency setting signal gain frequency)
settings do not change. Set Pr. 125 and Pr. 126 to adjust the gains.
Under PM motor control, if the protective function (E.OLT) is activated due to insufficient torque in
the low-speed range, set longer acceleration/deceleration times only in the low-speed range in
Pr. 791 "Acceleration time in low-speed range" and Pr. 792 "Deceleration time in low-speed range".
NOTES
Pr. 21 setting does not affect the minimum increment setting of Pr. 611 "Acceleration time at a
restart".
The parameter can be set in five digits including the numbers below decimal point for the
FR-DU08 and the FR-PU07. A "1000" or more value is set in increments of 0.1 s even if Pr. 21 = "1".
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......