Fine adjustment after PID gain tuning
If fine adjustment is required after completion of PID gain tuning, adjust the proportional band
(Pr. 129 or Pr. 756), integral time (Pr. 130 or Pr. 757), and differential time (Pr. 134 or Pr. 758).
Status of measurement values
Adjustment method
The response is fast, but vibrations are observed.
Increase the proportional band (Pr. 129 or Pr. 756).
(Smaller proportional effect)
Increase the integral time (Pr. 130 or Pr. 757).
(Smaller integral effect)
Optimal
—
Response is low
Decrease the proportional band (Pr. 129 or Pr. 756).
(Larger proportional effect)
Decrease the integral time (Pr. 130 or Pr. 757).
(Larger integral effect)
Tab. 5-186:
Adjustment methods after completion of PID gain tuning
NOTE
When the differential operation is used, adjust the differential time (Pr. 134 or Pr. 758) while check-
ing the stability and the response. (Increasing the differential time makes the differential effect
larger, and decreasing the differential time makes the differential effect smaller.)
Time
Measured value [%]
Set point
[%]
Time
Measured value [%]
Set point
[%]
Time
Measured value [%]
Set point
[%]
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......