(M) Monitor display and monitor output signal
Parameters
5 - 216
Calibration procedure for terminal FM when using the operation panel (FR-DU08)
Operation
Screen at power-ON
The monitor display appears.
Changing the operation mode
Press
to choose the PU operation mode. [PU] indicator is lit.
Calibration is also possible in the External operation mode.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
Calibration parameter selection
Turn
until
appears. Press
to display
.
"
Selecting the parameter number
Turn
until
(C0 (Pr. 900) FM/CA terminal calibration) appears. Press
to enable the parameter
setting. The monitored value of the item (initially the output frequency) selected by Pr. 54 FM/CA terminal function
selection will appear.
!
Pulse output via terminal FM
If stopped, press
or
to start the inverter operation. (To monitor the output frequency, motor
connection is not required.
When a monitor that does not require inverter operation is set in Pr. 54, calibration is also possible during a stop status.
Scale adjustment
Turn
to move the meter needle to a desired position.
&
Setting completed
Press
to enter the setting. The monitored value and
flicker alternately.
Turn
to read another parameter.
Press
to return to the
display.
Press
twice to show the next parameter.
Tab. 5-98:
FM terminal calibration
NOTES
Calibration can also be made for the External operation.Set the frequency in the External opera-
tion mode, and make calibration in the above procedure.
Calibration can be performed during operation.
For the operation from the parameter unit, refer to the Instruction Manual of the parameter unit.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......