(T) Multi-Function Input Terminal Parameters
Parameters
5 - 290
Start signal selection
NOTES
The STP (STOP) signal is assigned to the STP (STOP) terminal by the initial setting. Set "25" in any of
Pr. 178 to Pr. 189 to assign the STP (STOP) signal to another terminal.
When the JOG operation is enabled by turning ON the JOG signal, STP (STOP) signal will be disa-
bled.
Even when the output is stopped by turning ON the MRS signal, self-holding function is not can-
celled.
STF
STR
Pr. 250 setting and inverter condition
0 to 100 s, 9999
1000 s to 1100 s, 8888
OFF
OFF
Stop
Stop
OFF
ON
Reverse rotation
ON
OFF
Forward rotation
Forward rotation
ON
ON
Stop
Reverse rotation
Tab. 5-129:
Start signal selection
Parameters referred to
Pr. 4 to Pr. 6
(multi-speed setting)
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>