Parameters
(T) Multi-Function Input Terminal Parameters
FR-F800
5 - 279
5.9.8
Input terminal function selection
Use the following parameters to select or change the input terminal functions.
The initial value is for standard models.
The initial value is for separated converter types.
Pr.
Name
Initial
value
Initial signal
Setting range
178
T700
STF terminal function
selection
60
STF (Forward rotation command)
0 to 8, 10 to 14, 16, 18, 24, 25,
28, 37 to 40, 46 to 48, 50, 51,
60, 62, 64 to 67, 70 to 73, 77
to 81, 84, 94 to 98, 9999
179
T7001
STR terminal function
selection
61
STR (Reverse rotation command)
0 to 8, 10 to 14, 16, 18, 24, 25,
28, 37 to 40, 46 to 48, 50, 51,
61, 62, 64 to 67, 70 to 73, 77
to 81, 84, 94 to 98, 9999
180
T702
RL terminal function
selection
0
RL (Low-speed operation
command)
0 to 8, 10 to 14, 16, 18, 24, 25,
28, 37 to 40, 46 to 48, 50, 51,
62, 64 to 67, 70 to 73, 77 to
81, 84, 94 to 98, 9999
181
T703
RM terminal function
selection
1
RM (Middle-speed operation
command)
182
T704
RH terminal function
selection
2
RH (High-speed operation
command)
183
T705
RT terminal function
selection
3
RT (Second function selection)
184
T706
AU terminal function
selection
4
AU (Terminal 4 input selection)
185
T707
JOG terminal function
selection
5
JOG (Jog operation selection)
186
T708
CS terminal function
selection
9999
No function
187
T709
MRS terminal function
selection
24
MRS (Output stop)
10
X10 (Inverter run enable signal)
188
T710
STOP terminal function
selection
25
STP (STOP) (Start self-holding
selection)
189
T711
RES terminal function
selection
62
RES (Inverter reset)
Pr.
Name
Initial
value
Setting range
Description
699
T740
Input terminal filter
9999
5 to 50 ms
Set the time to delay the input terminal
response.
9999
No input terminal filter
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......