Parameters
(H) Protective function parameter
FR-F800
5 - 179
Setting for stall prevention operation in the high-frequency range
(Pr. 22, Pr. 23, Pr. 66)
●
When operating at the rated motor frequency or higher, acceleration may not be made because
the motor current does not increase. Also, when operating in the high-frequency range, the
current flowing to the locked motor becomes less than the rated output current of the inverter;
and even if the motor is stopped, the protective function will not operate (OL).
In a case like this, the stall prevention level can be reduced in the high-frequency range to improve
the motor's operating characteristics. This is useful when operating up to the high speed range,
such as when using a centrifuge. Normally, set Pr. 66 "Stall prevention operation reduction starting
frequency" to 60 Hz, and Pr. 23 "Stall prevention operation level compensation factor at double
speed" to 100%.
●
Calculation formula for stall prevention operation level
●
When Pr. 23 = "9999" (initial value), the stall prevention operation level is constant at the Pr. 22
level up to 590 Hz.
Fig. 5-66:
Stall prevention operation level
I002597E
Fig. 5-67:
Stall prevention operation level when
Pr. 22 = 150 %, Pr. 23 = 100 % and Pr. 66 = 60 Hz
I002598E
Stall prevention operation level (%)
in the high-frequency range
= A + B × [
Pr. 22 – A
] × [
Pr. 23 –1 00
]
Pr. 22 – B
100
Where A =
Pr. 66 (Hz) × Pr. 22 (%)
, B
=
Pr. 66 (Hz) × Pr. 22 (%)
Output frequency (Hz)
400 (Hz)
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Always at the Pr. 22 level
when Pr. 23 = "9999"
Stall prevention operation
level as set in Pr. 23
Stall p
rev
enti
on
oper
ati
o
n
lev
e
l (
%
)
Pr. 22
Pr. 66
400 Hz
Output frequency (Hz)
18
0
100
60
200
300
400
24
36
72
120
Stall
p
rev
en
ti
on
oper
a
tion
lev
e
l (
%
)
Output frequency (Hz)
Setting example (Pr. 22 = 150 %, Pr. 23 = 100 %, Pr. 66 = 60 Hz)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......