Parameters
(C) Motor constant parameters
FR-F800
5 - 311
90
C120
Motor constant (R1)
9999
0 to 50 Ω, 9999
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-EFS/MM-THE4
constant for the IPM motor MM-EFS/
MM-THE4, and the inverter internal
data for a PM motor other than MM-
EFS/MM-THE4.
92
C122
Motor constant (L1)/
d-axis inductance (Ld)
9999
93
C123
Motor constant (L2)/
q-axis inductance (Lq)
9999
859
C126
Torque current/
Rated PM motor current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
706
C130
Induced voltage constant
(phi f )
9999
Set this parameter according to the
PM motor specifications.
9999
The value calculated by the motor
constant parameter setting is used.
711
C131
Motor Ld decay ratio
9999
0 to 100%, 9999
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-EFS/MM-THE4
constant for the IPM motor MM-EFS/
MM-THE4, and the inverter internal
data for a PM motor other than MM-
EFS/MM-THE4.
712
C132
Motor Lq decay ratio
9999
0 to 100%, 9999
717
C182
Starting resistance tuning
compensation
9999
0 to 200%, 9999
721
C185
Starting magnetic pole
position detection pulse
width
9999
0 to 6000 μs,
10000 to 16000 μs, 9999
725
C133
Motor protection current
level
9999
100 to 500%
Set the maximum current (OCT) level
of the motor.
9999
Uses the MM-EFS/MM-THE4 constant
for the IPM motor MM-EFS/MM-THE4,
and 200% for a PM motor other than
MM-EFS/MM-THE4.
450
C200
Second applied motor
9999
0, 1, 3 to 6, 13 to 16, 20, 23, 24,
40, 43, 44, 50, 53, 54, 70, 73, 74,
210, 213, 214, 240, 243, 244,
8090, 8093, 8094, 9090, 9093,
9094
Set this parameter when using the
second motor.
(the same specifications as Pr. 71).
9999
The function is disabled.
453
C201
Second motor capacity
9999
Set the capacity of the second motor.
0 to 3600 kW
9999
V/F control
454
C202
Number of second motor
poles
9999
2, 4, 6, 8, 10, 12
Set the number of poles of the
second motor.
9999
V/F control
51
C203
Second electronic
thermal O/L relay
9999
0 to 500 A
Set the rated current of the second
motor.
0 to 3600 A
9999
Second electronic thermal O/L relay
disabled.
456
C204
Rated second motor voltage
200/400
0 to 1000 V
Set the rated voltage (V) of the
second motor.
457
C205
Rated second motor
frequency
9999
10 to 400 Hz
Set the rated frequency (Hz) of the
second motor.
9999
The MM-EFS/MM-THE4 constant is
used when the IPM motor MM-EFS/
MM-THE4 is selected for the second
motor, and the inverter internal data
is used when a PM motor other than
MM-EFS/MM-THE4 is selected. Use
the correct setting according to the
motor specification.
Pr.
Name
Initial
value
Setting range
Description
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......