Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 237
Speed detection hysteresis (Pr. 870)
●
This function prevents chattering of the speed detection signals. When an output frequency
fluctuates, the up to frequency signal (SU) and the speed detection signals (FB and FB2) may
repeat ON/OFF (chatter).
Setting hysteresis to the detected frequency prevents chattering of these signals.
Fig. 5-99:
Example of the speed detection (FB) signal
I002629E
I003032E
Fig. 5-100:
Example of the up to frequency (SU) signal
NOTES
In the initial setting, the FU signal is assigned to the terminal FU, and the SU signal is assigned to
the terminal SU.
All signals turn OFF during DC injection brake, and tuning at start-up.
Each signal's reference frequency differs by the control method.
Setting a higher value in Pr. 870 slows the response of frequency detection signals (SU, FB, FB2).
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 190 to Pr. 196
(output terminal function selection)
=>
FB
Pr. 42
OFF
OFF
ON
ON
ON
Output
frequency
(Hz)
Pr. 870
Pr. 41
Time
Output
frequency
(Hz)
SU output level
Set frequency
SU output level
SU signal
Pr. 870
Pr. 870
Pr. 870
Pr. 870
ON
ON
ON
Control method
Compared frequency
FU, FU2
FB, FB2, SU
V/F control
Output frequency
Output frequency
Advanced magnetic flux vector
control
Output frequency before the slip
compensation
Output frequency before the slip
compensation
PM motor control
Frequency command value
Estimated frequency (actual motor
speed)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......