(A) Application parameters
Parameters
5 - 352
●
Reverse action
When deviation X = (set point - measured value) is a plus value, the manipulated amount (output fre-
quency) is increased, and when the deviation is a minus value, the manipulated amount is decreased.
●
Forward action
When deviation X = (set point– measured value) is a minus value, the manipulated amount (output
frequency) is increased, and when the deviation is a plus value, the manipulated amount is decreased.
Relationship between deviation and manipulated amount (output frequency)
I002690E
Fig. 5-164:
Heating
I002691E
Fig. 5-165:
Cooling
PID action setting
Deviation
Plus
Minus
Reverse action
Forward action
Tab. 5-167:
Relationships between deviation and manipulated variable
X>0
X<0
+
-
Increase
[Heating]
Cold
Hot
Decrease
Deviation
Set point
Measured value
Feedback signal
(measured value)
Set point
X>0
X<0
+
-
Measured value
[Cooling]
Set point
Deviation
Too cold
Hot
Decrease
Increase
Set point
Feedback signal
(measured value)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......