(C) Motor constant parameters
Parameters
5 - 292
Setting the applied motor
Refer to the following list and set the parameters according to the applied motor.
Pr. 71
Pr.
450
Motor
Constant value range when
performing offline auto tuning
(increment)
Operational characteristic
of the electronic thermal O/L
relay
Stand-
ard
Constant
-torque
PM
0
(Pr. 71 initial
value)
Standard motor (such as SF-JR)
Pr. 82 (Pr. 455) and Pr. 859 (Pr. 860)
Pr. 90 (Pr. 458) and Pr. 91 (Pr. 459)
0 to 50 Ω, 9999 (0.001 Ω)
0 to 400 mΩ, 9999 (0.01 mΩ)
Pr. 92 (Pr. 460) and Pr. 93 (Pr. 461)
(Induction motor)
0 to 6000 mH, 9999 (0.1 mH)
0 to 400 mH, 9999 (0.01 mH)
Pr. 92 (Pr. 460) and Pr. 93 (Pr. 461)
(PM motor)
0 to 500 mH, 9999 (0.01 mH)
0 to 50 mH, 9999 (0.001 mH)
Pr. 94 (Pr. 462)
0 to 100%, 9999(0.01%)
Pr. 706 (Pr. 738)
0 to 5000 mV/(rad/s), 9999
(0.1 mV/(rad/s))
1
Constant-torque motor
(SF-JRCA, etc.)
2
⎯
Standard motor (such as SF-JR)
Adjustable 5 points V/F
(Refer to page 5-522.)
20
Mitsubishi standard motor
(SF-JR 4P 1.5 kW or lower)
40
Mitsubishi high-efficiency motor
SF-HR
50
Mitsubishi constant-torque motor
SF-HRCA
70
Mitsubishi high-performance
energy-saving motor SF-PR
210
IPM motor MM-EFS (1500 r/min
specification)/MM-THE4
240
IPM motor MM-EFS (3000 r/min
specification)
8090
IPM motor (other than MM-EFS/
MM-THE4)
9090
SPM motor
3 (4)
Standard motor (such as SF-JR)
Pr. 82 (Pr. 455), Pr. 859 (Pr. 860),
Pr. 90 (Pr. 458), Pr. 91 (Pr. 459),
Pr. 92 (Pr. 460), Pr. 93 (Pr. 461),
Pr. 94 (Pr. 462) and Pr. 706 (Pr. 738)
Internal data value 0 to 65534,
9999 (1)
The display increment can be
changed in Pr. 684.
13 (14)
Constant-torque motor (SF-JRCA,
etc.)
23 (24)
Mitsubishi standard motor
(SF-JR 4P 1.5 kW or lower)
43 (44)
Mitsubishi high-efficiency motor
SF-HR
53 (54)
Mitsubishi constant-torque motor
SF-HRCA
73 (74)
Mitsubishi high-performance
energy-saving motor SF-PR
213 (214)
IPM motor MM-EFS (1500 r/min
specification)/MM-THE4
IPM motor MM-EFS (3000 r/min
specification)
8093 (8094)
IPM motor (other than MM-EFS/
MM-THE4)
9093(9094)
SPM motor
Tab. 5-130:
Setting of parameter Pr. 71 and Pr. 450 (1)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......