![Mitsubishi Electric FR-F800 Скачать руководство пользователя страница 182](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884182.webp)
Parameter List
Parameters
5 - 20
PID c
o
ntr
o
l
1132
A626
Pre-charge change increment amount
0 to 100%, 9999
0.01%
9999
1133
A666
Second pre-charge change increment
amount
0 to 100%, 9999
0.01%
9999
1136
A670
Second PID display bias coefficient
0 to 500, 9999
0.01
9999
1137
A671
Second PID display bias analog value
0 to 300%
0.1%
20%
1138
A672
Second PID display gain coefficient
0 to 500, 9999
0.01
9999
1139
A673
Second PID display gain analog value
0 to 300%
0.1%
100%
1140
A664
Second PID set point/deviation input
selection
1 to 5
1
2
1141
A665
Second PID measured value input
selection
1 to 5, 101 to 105
1
3
1142
A640
Second PID unit selection
0 to 43, 9999
1
9999
1143
A641
Second PID upper limit
0 to 100%, 9999
0.1%
9999
1144
A642
Second PID lower limit
0 to 100%, 9999
0.1%
9999
1145
A643
Second PID deviation limit
0 to 100%, 9999
0.1%
9999
1146
A644
Second PID signal operation selection
0 to 3, 10 to 13
1
0
1147
A661
Second output interruption detection
time
0 to 3600 s, 9999
0.1 s
1
1148
A662
Second output interruption detection
level
0 to 590 Hz
0.01 Hz
0 Hz
1149
A663
Second output interruption cancel level
900 to 1100%
0.1%
1000%
PL
C
fu
n
ct
io
n
1150
to
1199
A810
to
A859
PLC function user parameters 1 to 50
0 to 65535
1
0
PID gain tuning
1211
A690
PID gain tuning timeout time
1 to 9999 s
1 s
100 s
1212
A691
Step manipulated amount
900 to 1100%
0.1%
1000%
1213
A692
Step response sampling cycle
0.01 to 600 s
0.01 s
1 s
1214
A693
Timeout time after the maximum slope
1 to 9999 s
1 s
10 s
1215
A694
Limit cycle output upper limit
900 to 1100%
0.1%
1100%
1216
A695
Limit cycle output lower limit
900 to 1100%
0.1%
1000%
1217
A696
Limit cycle hysteresis
0.1 to 10%
0.1%
1%
1218
A697
PID gain tuning setting
0, 100 to 102, 111, 112,
121, 122, 200 to 202, 211,
212, 221, 222
1
0
1219
A698
PID gain tuning start/status
(0), 1, 8, (9, 90 to 96)
1
0
⎯
1300
to
1343,
1350
to
1359
N500
to
N543,
N550
to
N559
Communication option parameters.
For details, refer to the Instruction Manual of the option.
PID c
o
n
tr
o
l
enhanc
e
d
func
tions
1361
A440
Detection time for PID output hold
0 to 900 s
0.1 s
5 s
1362
A441
PID output hold range
0 to 50%, 9999
0.1%
9999
1363
A447
PID Priming time
0 to 360 s, 9999
0.1 s
9999
1364
A448
Stirring time during sleep
0 to 3600 s
0.1 s
15 s
1365
A449
Stirring interval time
0 to 1000 h
0.1 h
0 h
1366
A627
Sleep boost level
0 to 100%, 9999
0.01%
9999
Fu
n
c
ti
o
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to page
Cu
st
o
m
e
r
setting
FM
CA
Tab. 5-2:
Parameter overview (by number) (19)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......