(N) Operation via communication and its settings
Parameters
5 - 506
●
Parameter
Pr.
Register
Parameter name
Read/Write
Remarks
0 to 999
41000 to
41999
Refer to the parameter list (page 5-2)
for the parameter names.
Read/write
The parameter 41000
is the register number.
C2 (902)
41902
Terminal 2 frequency setting bias
(frequency)
Read/write
C3 (902)
42092
Terminal 2 frequency setting bias
(analog value)
Read/write
Analog value (%) set to C3 (902) .
43902
Terminal 2 frequency setting bias
(terminal analog value)
Read
Analog value (%) of the voltage
(current) applied to the terminal
2 .
125 (903)
41903
Terminal 2 frequency setting gain
(frequency)
Read/write
C4 (903)
42093
Terminal 2 frequency setting gain
(analog value)
Read/write
Analog value (%) set to C4 (903) .
43903
Terminal 2 frequency setting gain
(terminal analog value)
Read
Analog value (%) of the voltage
(current) applied to the terminal
2 .
C5 (904)
41904
Terminal 4 frequency setting bias
(frequency)
Read/write
C6 (904)
42094
Terminal 4 frequency setting bias
(analog value)
Read/write
Analog value (%) set to C6 (904) .
43904
Terminal 4 frequency setting bias
(terminal analog value)
Read
Analog value (%) of the current
(voltage) applied to the terminal
4 .
126 (905)
41905
Terminal 4 frequency setting gain
(frequency)
Read/write
C7 (905)
42095
Terminal 4 frequency setting gain
(analog value)
Read/write
Analog value (%) set to C7 (905) .
43905
Terminal 4 frequency setting gain
(terminal analog value)
Read
Analog value (%) of the current
(voltage) applied to the terminal
4 .
C12 (917)
41917
Terminal 1 bias frequency (speed)
Read/write
C13 (917)
42107
Terminal 1 bias (speed)
Read/write
Analog value (%) set to C13
(917)
43917
Terminal 1 bias (speed)
(terminal analog value)
Read
Analog value (%) of the voltage
applied to the terminal 1
C14 (918)
41918
Terminal 1 gain frequency (speed)
Read/write
C15 (918)
42108
Terminal 1 gain (speed)
Read/write
Analog value (%) set to C15(918)
43918
Terminal 1 gain (speed)
(terminal analog value)
Read
Analog value (%) of the voltage
applied to the terminal 1
C16 (919)
41919
Terminal 1 bias command (torque)
Read/write
C17 (919)
42109
Terminal 1 bias (torque)
Read/write
Analog value (%) set to C17
(919)
43919
Terminal 1 bias (torque)
(terminal analog value)
Read
Analog value (%) of the voltage
applied to the terminal 1
C18 (920)
41920
Terminal 1 gain command (torque)
Read/write
C19 (920)
42110
Terminal 1 gain (torque)
Read/write
Analog value (%) set to C19
(920)
43920
Terminal 1 gain (torque)
(terminal analog value)
Read
Analog value (%) of the voltage
applied to the terminal 1
C8 (930)
41930
Current output bias signal
Read/write
C9 (930)
42120
Current output bias current
Read/write
Analog value (%) set to C9 (930)
C10 (931)
41931
Current output gain signal
Read/write
C11 (931)
42121
Current output gain current
Read/write
Analog value (%) set to C11
(931)
C38 (932)
41932
Terminal 4 bias command (torque)
Read/write
C39 (932)
42122
Terminal 4 bias (torque)
Read/write
Analog value (%) set to C39
(932)
43932
Terminal 4 bias (torque)
(terminal analog value)
Read
Analog value (%) of the current
(voltage) applied to the terminal
4
Tab. 5-272:
Parameter
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......