When using the cleaning function for the purpose of periodic maintenance in such applications
that require continuous pump operation for a long time, use a time trigger. The time trigger is
enabled by setting a time period before starting the cleaning operation in Pr. 1479 "Cleaning time
trigger". The timer starts when the timer starting condition is satisfied, and the cleaning operation
is performed at a time interval set in Pr. 1479.
●
Starting conditions of the timer for a time trigger
–
When the start command turns ON
–
When the cleaning ends
Cleaning operation by the cleaning signal (X97 signal)
●
When the X97 signal is assigned to an input terminal, the cleaning operation can be finished when
the cleaning signal (X97) is turned from ON to OFF.
●
For the X97 signal input, set "97" in any of Pr. 178 to Pr. 189 to assign the function.
I003039E
Fig. 5-158:
Starting conditions of the timer for a time trigger
Pr. 1470 setting
X97 signal
Cleaning
operation
Cleaning end condition
Assignment
ON/OFF
0
Optional
Optional
Invalid
—
Other than 0
Not assigned
—
Enabled
After cleaning is performed for the
number of times set in Pr. 1470
Assigned
OFF
Invalid
—
ON
Enabled
After cleaning is performed for
the number of times set in
Pr. 1470
When X97 signal turns OFF
Tab. 5-166:
Finishing the cleaning operation with cleaning signal (X97)
Y215
STF
Output
frequency
ON
Cleaning
operation
(Pr. 1470 = Once)
ON
ON
ON
0 Hz
Normal
operation
Cleaning
operation
(Pr. 1470 = Once)
Normal
operation
Cleaning
operation
(Pr. 1470 = Once)
Normal
operation
Time
Time trigger
Time trigger
Start command ON trigger
Pr. 1479
Pr. 1479
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......