Parameters
(E) Environment setting parameters
FR-F800
5 - 89
●
The life alarm signal (Y90) turns ON when any of the control circuit capacitor, main circuit capacitor,
cooling fan or inrush current limit circuit reaches the life alarm output level.
●
For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of
Pr. 190 to Pr. 196 (output terminal function selection).
Life display of the inrush current limit circuit (Pr. 256) (Standard models)
●
The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr. 256.
●
The number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down
from 100% (0 time) every 1%/10,000 times. As soon as 10% (900,000 times) is reached, Pr. 255 bit
3 is turned ON and also a warning is output to the Y90 signal.
Life display of the control circuit capacitor (Pr. 257)
●
The deterioration degree of the control circuit capacitor is displayed in Pr. 257.
●
In the operating status, the control circuit capacitor life is calculated from the energization time
and temperature, and is counted down from 100%. As soon as the control circuit capacitor life
falls below 10%, Pr. 255 bit 0 is turned ON and also a warning is output to the Y90 signal.
Pr. 255
bit3
bit2
bit1
bit0
Decimal
Binary
15
1111
14
1110
×
13
1101
×
12
1100
×
×
11
1011
×
10
1010
×
×
9
1001
×
×
8
1000
×
×
×
7
0111
×
6
0110
×
×
5
0101
×
×
4
0100
×
×
×
3
0011
×
×
2
0010
×
×
×
1
0001
×
×
×
0
0000
×
×
×
×
: With warnings, ×: Without warnings
Tab. 5-43:
Displaying the end of service life by bits
NOTES
When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life can be output separately
to the control circuit capacitor life signal (Y86), main circuit capacitor life signal (Y87), cooling fan
life signal (Y88), and inrush current limit circuit life signal (Y89).
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......