(M) Monitor display and monitor output signal
Parameters
5 - 230
Take caution when changing the frequency setting with an analog signal or the setting dial of the
operation panel (FR-DU08), because this change speed and the timing of the change speed
determined by the acceleration/deceleration time setting may cause the output of the SU (up to
frequency) signal to switch repeatedly between ON and OFF. (This repeating does not occur when
the acceleration/deceleration time setting is "0 s".)
The setting is available only for standard models.
This signal cannot be assigned to the output terminals for plug-in options (FR-A8AY, FR-A8AR).
Available when the plug-in option is connected.
"
This can be set for Pr. 313 to Pr. 322 when an option (FR-A8AY, FR-A8AR, FR-A8NC, or FR-A8NCE) is
installed. For the corresponding parameters of each option, refer to the Instruction Manual of the
option.When the power is reset, the fault output 2 signal (ALM2) turns OFF at the same time as the
power turns OFF.
206
306
Y206
Cooling fan operation
command signal
Output when the cooling fan operation is
commanded.
Pr. 244
207
307
Y207
Control circuit
temperature signal
Output when the temperature of the
control circuit board reaches the
detection level or higher.
Pr. 663
208
308
PS
PU stopped signal
Output while the PU is stopped.
Pr. 75
211
311
LUP
Upper limit warning
detection
Output when the load fault upper limit
warning is detected.
Pr. 1480 to
Pr. 1492
212
312
LDN
Lower limit warning
detection
Output when the load fault lower limit
warning is detected.
213
313
Y213
During load
characteristics
measurement
Output during measurement of the load
characteristics.
215
315
Y215
During cleaning
Output during operation of the cleaning
function.
Pr. 1469 to
Pr. 1479
217
317
Y217
Priming pump operation
Outputs the signal for starting the
priming pump.
Pr.1363
218
318
STIR
Stirring
Output during the stirring operation.
Pr.1364, Pr.1365
219
319
Y219
PID upper/lower limit
pre-warning
Output when the PID measured value
meets the requirements of the limit pre-
warning signal output conditions.
Pr.1370 to
Pr.1373
220
320
Y220
Second PID upper/lower
limit pre-warning
226
326
Y226
Auxiliary pressure pump
operation
Output when the PID deviation exceeds
the auxiliary pressure pump operation
starting level.
Pr.1374, Pr.1375
228
328
DRY
Dry run
Output when a dry-run state is detected.
Pr.42, Pr.43,
Pr.132, Pr.1144,
Pr.1370
229
329
Y229
PID input pressure
warning
Output when the pump inlet pressure
reaches the warning level.
Pr.1370,
Pr.1373,
Pr.1377,
Pr.1378, Pr.1380
230
330
Y230
PID input pressure fault
Output when the pump inlet pressure
reaches the fault level.
Pr.1370,
Pr.1377,
Pr.1379, Pr.1381
9999
⎯
No function
⎯
⎯
⎯
Setting
Signal
name
Function
Operation
Related
parameter
Refer to
page
Positive
logic
Negative
logic
Tab. 5-101:
Output terminal function assignment (4)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......