![Mitsubishi Electric FR-F800 Скачать руководство пользователя страница 208](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884208.webp)
Control method
Parameters
5 - 46
Initializing the parameters required for the PM motor control (Pr. 998)
●
PM parameter initialization sets parameters required for driving an IPM motor MM-EFS or MM-THE4.
●
The offline auto tuning enables the operation with an IPM motor other than MM-EFS or MM-THE4
and with SPM motors.
●
Two MM-EFS or MM-THE4 IPM parameter initialization methods are available; setting Pr. 998 "PM
parameter initialization", and selecting
(IPM parameter initialization) mode on the opera-
tion panel.
●
To use a motor capacity that is one rank lower than the inverter capacity, set Pr. 80 "Motor capacity"
before performing IPM parameter initialization.
●
When Pr. 998 = "12, 14, 8009, or 9009", the monitor is displayed and the frequency is set using the
motor rotations per minute. To use frequency to display or set, set Pr. 998 = "112, 114, 8109, or
9109".
●
Set Pr. 998 = "0" to change the PM motor control parameter settings to the parameter settings
required to drive an induction motor.
●
When using an IPM motor other than MM-EFS/MM-THE4, set Pr. 998 = "8009, 8109, 9009, or 9109".
The setting can be made after performing offline auto tuning.
Pr.
Name
Initial
value
Setting
range
Description
998
E430
PM parameter
initialization
0
0
Parameter settings for an induction motor
(frequency)
The parameter settings
required to drive an
induction motor are set.
12
For IPM motor MM-EFS (1500 r/min
specification)/MM-THE4.
Parameter setting (rotations per minute)
The parameters settings
required to drive an IPM
motor are set.
14
For IPM motor MM-EFS (3000 r/min
specification).
Parameter setting (rotations per minute)
112
For IPM motor MM-EFS (1500 r/min
specification)/MM-THE4.
Parameter setting (frequency)
114
For IPM motor MM-EFS (3000 r/min
specification)
Parameter setting (frequency)
8009
The parameters settings required to drive
an IPM motor other than MM-EFS/MM-
THE4 are set.
(rotations per minute) (after tuning)
The parameters settings
required to drive an IPM
motor are set.
(Set Pr. 71 "Applied motor"
and perform offline auto
tuning in advance.
(Refer to page 5-310.))
8109
The parameters settings required to drive
an IPM motor other than MM-EFS/MM-
THE4 are set.
(frequency) (after tuning)
9009
The parameters settings required to drive
an SPM motor are set.
(rotations per minute) (after tuning)
The parameters settings
required to drive an SPM
motor are set.
(Set Pr. 71 "Applied motor"
and perform offline auto
tuning in advance.
(Refer to page 5-310.))
9109
The parameters settings required to drive
an SPM motor are set.
(frequency) (after tuning)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......