(A) Application parameters
Parameters
5 - 330
●
The input signals are as shown below.
For separated converter types, the X10 signal is assigned to the terminal MRS in the initial setting.
For the MRS signal, set "24" to any of Pr. 180 to Pr. 189 (input terminal function selection) to assign
the function to another terminal.
When the MRS signal is OFF, neither the commercial power supply operation nor the inverter
operation can be performed.
Terminal CS is initially set to "no function". To enable CS signal, set "6" in Pr.186 CS terminal function
selection to assign the function to a terminal. The CS signal operates only when the MRS signal is
ON.
STF(STR) operates only when the MRS and CS signals are both ON.
"
The RES signal can be used for reset input acceptance with Pr. 75 "Reset selection/disconnected
PU detection/PU stop selection". When RES signal and another input signal are simultaneously
input, the MC operation by the RES signal has a higher priority.
!
MC1 turns OFF at an inverter fault.
When Pr. 138 = "0 (electronic bypass invalid at a fault)", MC2 is OFF. When Pr. 138 = "1 (electronic
bypass valid at a fault)", MC2 is ON.
&
MC operation
: MC-ON
×: MC-OFF
⎯
:
During inverter operation, MC2-OFF, MC3-ON
During commercial power supply operation, MC2-ON, MC3-OFF
Invariance:
The status before changing the signal ON or OFF is held.
Signal
Applied
terminal
Function
Operation
MC operation
MC1
MC2
MC3
MRS
Selects whether or not
operation is available.
ON ....... Electronic bypass
operation
available
⎯
⎯
OFF ...... Electronic bypass
operation not
available
×
Invariance
CS
CS
Inverter/commercial
power supply operation
switchover
ON ....... Inverter operation
×
OFF ...... Commercial power
supply operation
×
STF
(STR)
STF
(STR)
Inverter operation
command
(Disabled during
commercial power supply
operation)
ON ....... Forward rotation
(reverse rotation)
×
OFF ...... Stop
×
OH
Set one of Pr. 180
to Pr. 189 to "7".
External thermal relay
input
ON ....... Motor normal
⎯
⎯
OFF ...... Motor fault
×
×
×
RES
RES
ON ....... Reset
Invariance
×
Invariance
OFF ...... Normal operation
⎯
⎯
X95/X96
Set "95" and "96"
in any of Pr.180
to Pr.189.
Converter unit fault /
Converter unit fault
(E.CPU, E.OHT)
X95 signal OFF,
X96 signal OFF
Converter fault
(E.OHT, E.CPU)
×
×
×
X95 signal ON,
X96 signal ON
Converter normal
⎯
⎯
X95 signal OFF,
X96 signal ON
Converter fault (other
than E.OHT or E.CPU)
×
⎯
×
Tab. 5-158:
Input signals
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......