Check first when you have a trouble
Protective functions
6 - 38
6.6.9
Operation mode is not changed properly
6.6.10
Operation panel (FR-DU08) display is not operating
6.6.11
Motor current is too large
Check
points
Possible cause
Countermeasure
Refer to
page
Input
signal
Start signal (STF or STR) is ON.
Check that the STF and STR signals are off.
When either is ON, the operation mode cannot
be changed.
Parameter
setting
Pr. 79 "Operation mode selection" setting is
improper.
When the Pr. 79 is set to "0 (initial value)", the
operation mode is the External operation mode
at power ON. To switch to the PU operation
mode, press PU/EXT key on the operation panel
(press PU key on the parameter unit (FR-PU07)).
At other settings (1 to 4, 6, 7), the operation
mode is limited accordingly.
Operation mode and a writing device do
not correspond.
Check Pr. 79 "Operation mode selection", Pr. 338
"Communication operation command source",
Pr. 339 "Communication speed command
source", Pr. 550 "NET mode operation command
source selection" and Pr. 551 "PU mode
operation command source selection", and
select an operation mode suitable for the
purpose.
Check
points
Possible cause
Countermeasure
Refer to
page
Main
circuit
Power is not input.
Input the power.
Control
circuit
Front
cover
Operation panel is not properly connected
to the inverter.
Check if the inverter front cover is installed
securely.
Check
points
Possible cause
Countermeasure
Refer to
page
Parameter
setting
Torque boost (Pr. 0, Pr. 46) setting is
improper under V/F control, so the stall
prevention function is activated.
Increase/decrease the Pr. 0 "Torque boost"
setting value by 0.5% increments so that stall
prevention does not occur.
V/F pattern is improper when V/F control is
performed.
(Pr. 3, Pr. 14, Pr. 19)
Set rated frequency of the motor to Pr. 3 "Base
frequency".
Use Pr. 19 "Base frequency voltage" to set the
base voltage (for example, rated motor
voltage).
Change Pr. 14 "Load pattern selection"
according to the load characteristic.
Stall prevention function is activated due to
a heavy load.
Reduce the load weight.
⎯
Set Pr. 22 "Stall prevention operation level"
higher according to the load. (If Pr. 22 is set too
high, an overcurrent trip (E.OC
) is likely to
occur.)
Check the capacities of the inverter and the
motor.
⎯
Offline auto tuning is not performed under
Advanced magnetic flux vector control.
Perform offline auto tuning.
When PM motor control is selected for a PM
motor other than MM-EFS/MM-THE4, and
offline auto tuning is not performed.
Perform offline auto tuning for a PM motor.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......