Appendix
For customers using HMS network options
FR-F800
A - 23
A.4
For customers using HMS network options
A.4.1
List of inverter monitored items / command items
The following items can be set using a communication option.
16bit data
No.
Description
Unit
Type
Read/write
H0000 No
data
⎯
⎯
⎯
H0001
Output frequency
0.01 Hz
unsigned
R
H0002
Output current
0.01 A/0.1 A
unsigned
R
H0003 Output
voltage
0.1
V unsigned
R
H0004 reserved
⎯
⎯
⎯
H0005
Frequency setting value
0.01 Hz
unsigned
R
H0006
Motor speed
1 r/min
unsigned
R
H0007 Motor
torque
0.1% unsigned
R
H0008
Converter output voltage
0.1 V
unsigned
R
H0009 reserved
⎯
⎯
⎯
H000A
Electric thermal relay function load factor
0.1%
unsigned
R
H000B
Output current peak value
0.01 A/0.1 A
unsigned
R
H000C
Converter output voltage peak value
0.1 V
unsigned
R
H000D Input
power
0.01
kW/0.1
kW
unsigned
R
H000E Output
power
0.01
kW/0.1
kW
unsigned
R
H000F
Input terminal status
⎯
⎯
R
H0010
Output terminal status
⎯
⎯
R
H0011 Load
meter
0.1% unsigned
R
H0012
Motor excitation current
0.01 A/0.1 A
unsigned
R
H0013 reserved
⎯
⎯
⎯
H0014
Cumulative energization time
1 h
unsigned
R
H0015 reserved
⎯
⎯
⎯
H0016 Orientation
status
1
unsigned
R
H0017
Actual operation time
1 h
unsigned
R
H0018
Motor load factor
0.1%
unsigned
R
H0019 Cumulative
power
1
kWh unsigned
R
H001A to
H0021
reserved
⎯
⎯
⎯
H0022 Motor
output
0.1
kW unsigned
R
H0023 to
H0025
reserved
⎯
⎯
⎯
H0026
Trace status
⎯
unsigned R
H0027
reserved
⎯
⎯
⎯
H0028
PLC function user monitor 1
⎯
unsigned R
H0029
PLC function user monitor 2
⎯
unsigned R
H002A
PLC function user monitor 3
⎯
unsigned R
H002B to
H002D
reserved
⎯
⎯
⎯
H002E Motor
temperature
R
H002F to
H0031
reserved
⎯
⎯
⎯
H0032
Power saving effect
⎯
unsigned R
H0033
Cumulative saving power
⎯
unsigned R
H0034
PID set point
0.1%
unsigned
R/W
H0035
PID measured value
0.1%
unsigned
R/W
Tab. A-4:
Inverter monitored items (16bit data) (1)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......