Parameters
(C) Motor constant parameters
FR-F800
5 - 291
5.10
(C) Motor constant parameters
5.10.1 Applied
motor
By setting the applied motor type, the thermal characteristic appropriate for the motor can be selected.
When using a constant-torque or PM motor, the electronic thermal O/L relay is set according to the
used motor.
If the Advanced magnetic flux vector control or PM motor control is selected, the motor constant nec-
essary for control (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA, MM-EFS, MM-THE4, etc.) is also selected at
the same time.
Purpose
Parameter to set
Refer to
page
To select the motor to be used
Applicable motor
P.C100, P.C200
Pr. 71, Pr. 450
To run by maximizing the performance
of the induction motor
Offline auto tuning
P.C000,
P.C100 to P.C105,
P.C107, P.C108,
P.C110,
P.C120 to P.C126,
P.C200 to P.C205,
P.C207, P.C208,
P.C210,
P.C220 to P.C226
Pr. 9, Pr. 51, Pr. 71,
Pr. 80 to Pr. 84,
Pr. 90 to Pr. 94, Pr. 96,
Pr. 453 to Pr. 463,
Pr. 684, Pr. 707, Pr. 724,
Pr. 744, Pr. 745, Pr. 859,
Pr. 860
To run by maximizing the performance
of the PM motor
PM motor offline auto
tuning
P.C000,
P.C100 to P.C108,
P.C110, P.C120,
P.C122, P.C123,
P.C126,
P.C130 to P.C133,
P.C150, P.C182,
P.C185,
P.C200 to P.C208,
P.C210, P.C220,
P.C222, P.C223,
P.C226,
P.C230 to P.C233,
P.C282, P.C285
Pr. 9, Pr. 51, Pr. 71,
Pr. 80, Pr. 81, Pr. 83,
Pr. 84, Pr. 90, Pr. 92,
Pr. 93, Pr. 96, Pr. 450,
Pr. 453, Pr. 454, Pr. 456
to Pr. 458, Pr. 460,
Pr. 461, Pr. 463, Pr. 684,
Pr. 702, Pr. 706, Pr. 707,
Pr. 711, Pr. 712, Pr. 717,
Pr. 721, Pr. 724, Pr. 725,
Pr. 738 to Pr. 747,
Pr. 788, Pr. 859, Pr. 860,
Pr. 1002
To perform high accuracy operation
without being affected by
temperature and high-torque/ultra-
low speed
Online auto tuning
P.C111, P.C211
Pr. 95, Pr. 574
Pr.
Name
Initial value
Setting range
Description
71
C100
Applied motor
0
0 to 6, 13 to 16, 20, 23,
24, 40, 43, 44, 50, 53, 54,
70, 73, 74, 3210, 213,
214, 240, 243, 244, 8090,
8093, 8094, 9090, 9093,
9094
By selecting a motor, the thermal
characteristic and motor constant
of each motor are set.
450
C200
Second applied motor
9999
0, 1, 3 to 6, 13 to 16, 20,
23, 24, 40, 43, 44, 50, 53,
54, 70, 73, 74, 210, 213,
214, 240, 243, 244, 8093,
8094, 9090, 9093, 9094
Set it when using the second
motor.
(the same specifications as Pr. 71)
9999
The function is disabled.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......