Parameters
(N) Operation via communication and its settings
FR-F800
5 - 497
Node with network bias resistors
●
This product is a node with local bias resistors. Therefore at least one node must be a node with
network bias resistors in the network configuration.
●
When configuring the network with only this products, refer to the following, and make the node
with network bias resistors. (When using two sets in one segment, insert them into both ends of
the network.)
BACnet reception status monitor (Pr. 52)
Set Pr. 52 = "81" to monitor the BACnet communication status on the operation panel.
I003073E
Fig. 5-242:
Connecting the network bias resistors to the frequency inverter
Monitor
value
Status
Description
LF signal
output
0
Idle
Never had BACnet communication
OFF
1
Automatic baud rate
recognition
Automatic baud rate recognition (
Communication error during automatic baud rate recognition
is not counted)
OFF
2
Not joined the network
Waiting for a token to the own node
OFF
10
Data to the own node
Received a token to the own node
OFF
11
Received a supported request to the own node (including
broadcasting)
OFF
12
Received an unsupported request to the own node (including
broadcasting)
OFF
20
Data to the other node
Received a token to other nodes
OFF
30
Node separated
Separated from token passing after joined in it
OFF
90
Error data
Detected a communication error
ON
91
Protocol error
(LPDU, NPDU, APDU are not following the format regulations.)
ON
Tab. 5-261:
BACnet status monitor
+
-
+ TXD
RXD
-
VCC
GND
+
-
+ TXD
RXD
-
VCC
GND
RDA1
(RXD1+)
RDB1
(RXD1-)
RDA2
(RXD2+)
RDB2
(RXD2-)
SDA1
(TXD1+)
SDB1
(TXD1-)
SDA2
(TXD2+)
SDB2
(TXD2-)
P5S
(VCC)
SG
(GND)
P5S
(VCC)
SG
(GND)
510
Ω
510
Ω
Other
node
Connect two 510
Ω
(1/4W) resistor.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......