Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 233
●
When using the RY, RUN, and RUN3 signals, refer to the following and assign the functions by Pr.
190 to Pr. 196 (output terminal function selection).
Fault output signals (ALM, ALM2)
●
The Fault (ALM, ALM2) signals are output when the inverter protective function is activated.
●
The ALM2 signal stays ON during the reset period after the fault occurs.
●
To use the ALM2 signal, set "94 (positive logic) or 194 (negative logic)" in any of Pr. 190 to Pr. 196
(output terminal function selection) to assign the function to the output terminal.
●
The ALM signal is assigned to the A1B1C1 contacts in the initial status.
Output signal
Pr. 190 to Pr. 196 settings
Positive logic
Negative logic
RY
11
111
RUN
0
100
RUN3
45
145
Tab. 5-103:
Assignment of the signals
NOTE
The RUN signal (positive logic) is assigned to the terminal RUN in the initial status.
I001153E
Fig. 5-96:
Fault signals
NOTE
For the inverter fault details, refer to page 6-9.
Inverter alarm occurrence (trip)
Output
fr
eque
nc
y
ALM
Reset ON
Time
RES
ALM2
Reset processing
(about 1s)
ON
ON
ON
OFF
OFF
OFF
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......