Parameters
(T) Multi-Function Input Terminal Parameters
FR-F800
5 - 261
Relationship between the analog input terminal function and the calibration parameter
●
Calibration parameter according to the terminal 1 function
●
Calibration parameter according to the terminal 4 function
Use Pr. 148 "Stall prevention level at 0 V input" and Pr. 149 "Stall prevention level at 10 V input" to
adjust the bias and gain for stall prevention operation level under V/F control and Advanced
magnetic flux vector control.
To change the frequency for the maximum analog input (Pr. 125, Pr. 126)
●
To change only the frequency setting (gain) for the maximum analog input voltage (current), set
Pr. 125 (Pr. 126). (C2 (Pr. 902) to C7 (Pr. 905) settings do not need to be changed.)
Pr. 868
Setting
Terminal function
Calibration parameter
Bias setting
Gain setting
0
(initial
value)
Frequency (speed)
setting auxiliary
C2 (Pr. 902) "Terminal 2 frequency setting
bias frequency"
C3 (Pr. 902) "Terminal 2 frequency setting
bias"
C5 (Pr. 904) "Terminal 4 frequency setting
bias frequency"
C6 (Pr. 904) "Terminal 4 frequency setting
bias"
Pr. 125 "Terminal 2 frequency setting gain
frequency"
C4 (Pr. 903) "Terminal 2 frequency setting
gain"
Pr. 126 "Terminal 4 frequency setting gain
frequency"
C7 (Pr. 905) "Terminal 4 frequency setting
gain"
4
Stall prevention
operation level
/torque limit
C16 (Pr. 919) "Terminal 1 bias command
(torque)"
C17 (Pr. 919) "Terminal 1 bias (torque)"
C18 (Pr. 920) "Terminal 1 gain command
(torque)"
C19 (Pr. 920) "Terminal 1 gain (torque)"
9999
No function
⎯
⎯
Tab. 5-113:
Terminal 1 functional calibration parameter
Pr. 858
setting
Terminal function
Calibration parameter
Bias setting
Gain setting
0
(initial
value)
Frequency command
C5 (Pr. 904) "Terminal 4 frequency setting
bias frequency"
C6 (Pr. 904) "Terminal 4 frequency setting
bias"
Pr. 126 "Terminal 4 frequency setting gain
frequency"
C7 (Pr. 905)" Terminal 4 frequency setting
gain"
4
Stall prevention
operation level
/torque limit
C38 (Pr. 932) "Terminal 4 bias command
(torque)"
C39 (Pr. 932) "Terminal 4 bias (torque)"
C40 (Pr. 933) "Terminal 4 gain command
(torque)"
C41 (Pr. 933) "Terminal 4 gain (torque)"
9999
No function
⎯
⎯
Tab. 5-114:
Terminal 4 functional calibration parameter
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......