Control circuit
Installation and wiring
2 - 48
●
When using an external power supply for transistor output
– Sink logic
Use the terminal PC as a common terminal, and perform wiring as shown below. (Do not connect
terminal SD of the inverter with the terminal 0 V of the external power supply. When using
terminals PC-SD as a 24 V DC power supply, do not install an external power supply in parallel with
the inverter. Doing so may cause a malfunction in the inverter due to undesirable currents.)
– Source logic
Use the terminal SD as a common terminal, and perform wiring as shown below. (Do not connect
terminal PC of the inverter with the te24 V of the external power supply. When using
terminals PC-SD as a 24 V DC power supply, do not install an external power supply in parallel with
the inverter. Doing so may cause a malfunction in the inverter due to undesirable currents.)
Fig. 2-26:
Using an external power supply in connection with
the outputs of a PLC (sink logic)
I002371E
Fig. 2-27:
Using an external power supply in connection with
the outputs of a PLC (source logic)
I002372E
TB1
TB2
TB17
TB18
SD
PC
STR
STF
(SD)
Inverter
Current flow
Constant
voltage
circuit
QY40P type transistor
output unit
24 V DC
24 V DC
PC
TB1
TB2
TB17
TB18
STF
STR
SD
(SD)
Inverter
Current flow
Constant
voltage
circuit
QY80P type transistor
output unit
24 V DC
Fuse
24
V
DC
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......