Electro-magnetic interference (EMI) and leakage currents
Precautions for use of the inverter
3 - 8
Data line filter
Data line filter is effective as an EMI countermeasure.
Provide a data line filter for the detector cable, etc.
The impedance values above are reference values, and not guaranteed values.
쑶
EMI countermeasure example
Example
쑴
Data line filter: ZCAT3035-1330 (by TDK)
ESD-SR-250 (by NEC TOKIN)
Impedance (
Ω
)
10 to 100 MHz
100 to 500 MHz
80
150
Tab. 3-5:
Impedance (ZCAT3035-1330)
I002418E
Fig. 3-5:
Outline dimension drawing (ZCAT3035-1330)
I002419E
Fig. 3-6:
Noise reduction examples
NOTE
For compliance with the EU EMC Directive, refer to the Installation Guideline.
34
1
TDK
39
1
30
1
13
1
Lot number
Product name
Cable fixing band mount
[Unit: mm]
Inverter
Enclosure
Control
power
supply
Sensor
M
3~
Motor
Inverter
power
supply
Do not earth (ground) shield but connect it to signal
common cable.
Use a twisted pair shielded cable
EMC filter
Use 4-core cable for motor power cable and
use one cable as earth (ground) cable.
Install filter (FR-BLF, FR-BSF01)
on inverter output side.
Decrease carrier frequency
Separate inverter and
power line by more than
30 cm (at least 10 c m)
from sensor circuit.
Power
supply for
sensor
Do not earth (ground) control cable.
Do not earth (ground)
enclosure directly.
FR-BLF
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......