(A) Application parameters
Parameters
5 - 372
●
The PID gain tuning status can be checked with the read value of Pr. 1219 or the PID gain tuning
status monitor. The PID gain tuning status monitor is displayed instead of the output voltage
monitor.
●
When PID gain tuning is completed, the following parameters are automatically set.
●
To forcibly terminate the tuning during PID gain tuning, perform any of the following operations.
–
Turning OFF the PID gain tuning start/forced end signal (PGT).
–
Setting Pr. 1219 "PID gain tuning start/status" = "8".
–
Selecting the PID gain tuning forced end (8.END) in the function menu on the operation panel
(FR-DU08).
–
Turn the power supply OFF, reset the inverter, or turn OFF the start command.
Status monitor
PID gain tuning status
2
During tuning
3
Tuning completed
8
Tuning forced end
Tab. 5-183:
PID gain tuning status monitor
Pr.
Name
Step response method
Limit cycle method
P control
PI control
PID control
PI control
PID control
129 (756)
PID
130 (757)
PID integral
—
134 (758)
PID differential
time
—
—
—
: The calculation result is applied. —: "9999" is set.
Tab. 5-184:
Automatically set parameters after completion of PID gain tuning
NOTES
By PID gain tuning, the settings of the PID constant parameters (Pr. 129, Pr. 130, Pr. 134, Pr. 756 to
Pr. 758) are automatically changed. Before performing PID gain tuning, record the PID constant
parameter settings before tuning as required.
PID gain tuning also requires setting of the PID upper limit (Pr. 131 or Pr. 1143), PID lower limit
(Pr. 132 or Pr. 1144), PID deviation limit (Pr. 553 or Pr. 1145).
Changing the terminal assignment with Pr. 178 to Pr. 189 may affect other functions. Set parame-
ters after confirming the function of each terminal.
By PID gain tuning, the amount of operation is changed considerably. In some applications such
as a winding machine, materials may be affected.
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......