Specification comparison between PM motor control and induction motor control
Appendix
A - 4
For the motor capacity, the rated motor current should be equal to or less than the rated inverter
current. (It must be 0.4 kW or higher.)
If a motor with substantially low rated current compared with the rated inverter current is used,
speed and torque accuracies may deteriorate due to torque ripples, etc. Set the rated motor current
to about 40% or higher of the rated inverter current.
For the MM-EFS (1500 r/min specification), the number of motor poles differs between the 15 kW
or lower motor (6 poles) and the 18.5 kW or higher motor (8 poles). For this reason, the frequency
setting resolution also differs between them.
For the FR-F820-02330(55K) or lower and the FR-F840-01160(55K) or lower
For the FR-F820-03160(75K) or higher and the FR-F840-01800(75K) or higher
Output signal
Pulse output for
meter
In the initial setting, 1 mA is output at
the rated motor frequency from across
terminals FM and SD. (SD is a common
terminal.)
The permissible frequency load current
is 2 mA.
Pulse specification: 1440 pulses/s at the
rated motor frequency.
In the initial setting, 1 mA is output at
60 Hz from across terminals FM and SD.
(SD is a common terminal.)
The permissible frequency load current
is 2 mA.
Pulse specification: 1440 pulses/s at
60 Hz
Carrier frequency
Four patterns of 2 kHz, 6 kHz, 10 kHz, and
14 kHz
Selectable between 0.75 kHz to
14.5 kHz
Two patterns of 2 kHz and 6 kHz
0.75 kHz to 6 kHz
Automatic restart after
instantaneous power failure
No startup waiting time.
Using the regeneration avoidance
function or retry function together is
recommended.
Startup waiting time exists.
Startup delay
Startup delay of about 0.1 s for initial
tuning.
No startup delay
Driving by the commercial power
supply
Not available
Never connect an IPM motor to the
commercial power supply.
Can be driven by the commercial power
supply.
Operation during motor coasting
While the motor is coasting, potential is
generated across motor terminals.
Before wiring, make sure that the motor
is stopped.
While the motor is coasting, potential is
not generated across motor terminals.
Maximum motor wiring length
100 m or shorter
Overall length: 500 m or shorter
NOTES
Before wiring, make sure that the motor is stopped. Otherwise you may get an electric shock.
Never connect an IPM motor to the commercial power supply.
No slippage occurs with an IPM motor because of its characteristic. If an IPM motor, which took
over an induction motor, is driven at the same frequency as for the general-purpose motor, the
running speed of the IPM motor becomes faster by the amount of the general-purpose motor's
slippage. Adjust the speed command to run the IPM motor at the same speed as the induction
motor, as required.
Item
PM motor control
Induction motor control
Tab. A-2:
Differences between PM motor control and induction motor control (2)
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......