(A) Application parameters
Parameters
5 - 344
Set the load characteristics fault detection function. When the function is disabled, a trigger does
not occur. (Refer to page 5-184.)
"
The output signal can be used as a trigger if the signal is not assigned to a terminal.
!
When the automatic restart after instantaneous power failure is set for every start, or when the
online auto tuning is enabled, cleaning is started upon completion of the set operations.
While the self power management is enabled, the start trigger is disabled.
●
Convert a bit image (binary) of the trigger factor into a decimal value, and set the value in Pr. 1471.
●
Turning ON of X98 signal can be used as a trigger to start the cleaning operation. For the X98
signal input, set "98" in any of Pr. 178 to Pr. 189 to assign the function.
Pr. 1471
bit 3
bit 2
bit 1
bit 0
Decimal
Binary
15
1111
14
1110
×
13
1101
×
12
1100
×
×
11
1011
×
10
1010
×
×
9
1001
×
×
8
1000
×
×
×
7
0111
×
6
0110
×
×
5
0101
×
×
4
0100
×
×
×
3
0011
×
×
2
0010
×
×
×
1
0001
×
×
×
0
0000
×
×
×
×
: Trigger enabled, ×: Trigger disabled
Tab. 5-165:
Settings of Pr. 1471
I003038E
Fig. 5-157:
Bit 0 to 3 of Pr. 1471 setting
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1
15
7
0
bit
Set the decimal converted value of the bit image.
Pr. 1471 setting
bit 0 Start trigger
bit 1 Output current trigger
bit 2 PID upper/lower limit trigger
bit 3 Load warning trigger
Содержание FR-F800
Страница 2: ......
Страница 4: ......
Страница 28: ...Related manuals Introduction 1 8 ...
Страница 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Страница 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 720: ...Checking parameters changed from their initial values Initial value change list Parameters 5 558 ...
Страница 780: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 806: ...Outline dimension drawings Specifications 8 26 ...
Страница 833: ......